EasyManua.ls Logo

Fujitsu UTP-VX60A - Page 123

Fujitsu UTP-VX60A
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Suction Gas Temp Sensor Error
<TH4>
OK
DC
CN147
BLACK
BLACK
1 2 3 4
1 2 3 4
BLACK
BLACK
Suction gas temperature thermistor
Suction gas temperature thermistor short or open detected
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 17".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN147:1-2) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Suction gas temperature sensor (CN147:1-2)
Filter LED Continuous Flash.
Outdoor Unit : E. 75. 1
Error Code : 75
If the voltage does not appear, replace Main PCB and set up orignal address.
THERMISTOR
(HEX. EXT)
< TH5 >
THERMISTOR
(SUC. TEMP)
< TH4 >
Trouble shooting 45
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
E. 75.1
04-53

Table of Contents

Other manuals for Fujitsu UTP-VX60A

Related product manuals