02-12
Protective Function
Detect Parts
Operating Condition
Operation
Overcurrent Break
Stop
(Compressor)
Overcurrent
Protection Circuit
COOL HEAT
Compressor stopped
Heatsink Temp
Thermistor
<Pattern starting condition>
Heat sink temperature 95°C
<Pattern reset condition>
3 minutes have elapsed and heat sink temperature
Compressor stopped
Heatsink Temp
Protection Stop
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and heat sink temperature
Compressor stopped
Error display
<Patte
rn star
ting condition>
Current value Cooling: 14.8A (8,10HP) / 17.7A (12HP)
Heating: 23.5A
<Pattern reset condition>
Current value Cooling: 22.5A / Heating: 23.5A
Frequency Maximum
Setting Protection
(Compressor)
<Pattern starting condition>
Current value Cooling:
<Pattern reset condition>
Current value Cooling: 23.0A / Heating: 24.0A
Current Detector
Circuit
Compressor is stopped when the over currernt protectioncircuit in the
inverter PCBoad detects an abnormal current duringthe operation.
If it repeated 5 times, the compressor becomes permanentstop.
Compressor is stopped when the over current protection circuit in the
inverter PC Board detects an abnormal current at the time of start up.
Compressor becomes permanent stop if it re
peated over the number
of set time.
<Reset condition>
Error reset (push button SW) executed after power turned on again.
Compressor speed lowered
Compressor speed rise prohibited
Pattern and start current value changed by outside
temperature
DISPLAY
E941
E931
(permanent stop)
(permanent stop)
EAC4
Protective function
Detect device
Operation
Cool
Heat
Display
Outdoor Unit Reverse
phase, Missing phase
Wire Error
Main PCB
Reverse phase
prevention circuit
E615
Operating condition
1 Reverse phase prevention circuit detected reversed phase input or
input was not normal at the time of power ON.
2 Reverse phase prevention circuit detected open-phase after power ON.
Reverse phase prevention circuit detects normal condition
System Stop Error indication
<
Starting condition>
<
Reset condition>
74°C
74°C
15.8A (8,10HP) / 18.7A (12HP)

Table of Contents

Other manuals for Fujitsu UTP-VX60A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTP-VX60A and is the answer not in the manual?

Fujitsu UTP-VX60A Specifications

General IconGeneral
BrandFujitsu
ModelUTP-VX60A
CategoryAir Conditioner
LanguageEnglish

Related product manuals