Outdoor unit: AJ*072/090LELAH: 20A / AJ*108LELAH: 25A
Indoor unit:
20A
Leakage current: 100 mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit:
2.5mm
2
2 wires + Ground
Outdoor unit side: 400V 3 50Hz
Indoor unit side:
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Power
source
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Shall be checked and entered in the check sheet.
Shall be checked and entered in the check sheet.
Connection points check & loose terminal block screws check
0.33mm
2
, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed w
ithout a gap.
DIP SW : SET1 (1 ~4), Factory setting SET2, SET3,SET5-1,2,3: ALL OFF
T
Refer to the Installation manual 7.2.2
erminal resistor setting SET5 - 4 OFF: Disable, ON: Enable
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
There shall be no scratches, deformation, tilting, etc.
Shall be checked and entered in the check sheet.
Shall be installed positively.
Connection points check & loose terminal panel screws check
0.33mm
2
, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit add
ress (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
Indoor
unit
Outdoor
unit
Judgement standard
Check
Check contentsProcedure
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
01-03
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned
and will lead to trouble.
Circuit breaker capacity
Type of power source
wiring
Supply power source
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote contr
oller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Wiring on terminal blocks
Power cable: 6.0mm / Earth cable: 6.0mm
Limited wiring length : 62 m
Indoor unit:
2
2
2 wire type : 16 to 22AWG (0.33 to 1.25mm ) 3 wire type : 22AWG (0.33mm )
2 2
230V 1 50Hz

Table of Contents

Other manuals for Fujitsu UTP-VX60A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTP-VX60A and is the answer not in the manual?

Fujitsu UTP-VX60A Specifications

General IconGeneral
BrandFujitsu
ModelUTP-VX60A
CategoryAir Conditioner
LanguageEnglish

Related product manuals