Error Contents :
Transmission Error
Symptom :
LED repeats flashing 0.5sec ON & 1.0sec OFF.
Condition :
Normal communication with Indoor unit has been suspended for longer than 1 minute.
OK
Cause 3 : Ext. Switch Controller is defective.
Replace External Switch Controller.
OK
Cause 1 : DIP switch setting defective
Check setting of DIP-SW1-4, 1-5, 1-6.
Cause 2 : External noise
Remove or shut out external noise source.