EasyManua.ls Logo

Fujitsu UTP-VX60A - Page 167

Fujitsu UTP-VX60A
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trouble shooting 89
Refrigerant circuit address setting
error
Symptom :
Error Code display [ 2 6 ]
Cause 1 : Check of number of indoor unit registration refrigerant circuits
Check indoor unit registration.
(1) Number of refrigerant circuits of indoor unit registered at Replace Group Remote Controller is 3 refrigerant circuits or more
even though connected to one converter.
Make 2 refrigerant circuits or less
and wait 2 minutes
YES
NO
Replace Network Convertor
Replace Group Remote Controller
Condition of occurrence : Indoor unit registration is 3 refrigerant circuits or more.
Release condition : Indoor unit registration is 2 refrigerant circuits or less.
Error Contents :
Details :
Network Convertor (UTY-VGGXZ1) -
04-97

Table of Contents

Other manuals for Fujitsu UTP-VX60A

Related product manuals