F09 - Maximum setpoint allowed to the user (humidistat):
Electronic limits whose purpose is to prevent too high or too low setpoint humiditys are set.
F10 - Control differential (hysteresis) of the humidistat:
It is the difference of humidity (hysteresis) between turn ON and turn OFF the HUMID output.
It is the minimum time that the HUMID output will keep turned off, it means, the space of time between
the last stop and the next start.
It allows to adjust the time that HUMID output will keep turned on.
It allows to adjust the time that HUMID output will keep turned off.
[,f12] and [,f13]
F11 - M
F12 -
F13 -
,,,0]
[,,,1]
[,,,2]
[,,,3]
[,,,4]
[,,,5]
[,,,6]
[,,,7]
[,,,8]
[,,,9]
[,,10]
[,f15] [,f16] [,f17]
inimum delay to turn the humidistat output on:
Humidity output (time on):
Humidity output (time off):
Note: functions control a cyclical program (in seconds) for the humidistat output. This
cyclical program allows that pulverized water has time to transform in relative air humidity.
To disable this function, adjust the values to zero.
F14 - Auxiliary output operation mode (AUX):
[ Refrigeration
Heating
Dehumidification
Humidification
Intra-range alarm
Extra-range alarm
Independent cyclic timer
Cyclic timer operating only when the temperature reaches the setpoint (THERM output
deactivated)
Cyclic timer operating only when the humidity reaches the setpoint (HUMID output
deactivated)
Cyclic timer operating when the temperature or humidity reaches their setpoint
Cyclic timer operating only when the temperature and humidity reaches their setpoints
When changing the value of this function the following parameters will be automatically adjusted with
their default values: , , and setpoint for the AUX output.
F15 - Minimum setpoint allowed to the user (AUX output):
F16 - Maximum setpoint allowed to the user (AUX output):
Electronic limits whose purpose is to prevent that too high or too low setpoint values are set.
The limits will depend on the operation mode of the output adjusted in .
F17 - Control differential (hysteresis) of the AUX output:
It is the difference of temperature or humidity (hysteresis) between turn ON and turn OFF the AUX
output. This function depends on the operation mode of the output adjusted in .
F18 - Minimum delay to turn the AUX output on:
It is the minimum time that the AUX output will keep turned off, it means, the space of time between the
last stop and the next start.
Time base of AUX output timer:
Allows configuration of the on or off time scale for AUX output cyclic timer.
[,f14]
[,f14]
This time is valid only when AUX output is configured in the control mode
([,f14] configured in 0, 1, 2 or 3).
F19 -
F22 - Low room temperature alarm:
Temperature for activation of the low temperature alarm.
F23 - High room temperature alarm:
Temperature for activation of the high temperature alarm.
F24 - Low room humidity alarm:
Humidity for activation of the low humidity alarm.
F25 - High room humidity alarm:
Humidity for activation of the high humidity alarm.
F26 - Minimum delay to turn the AUX output on (alarm mode):
It is the minimum time that the AUX output will keep turned off after controller initialization. This time is
valid only when AUX output will be configured in the alarm mode ([,F14] configured in 4 or 5).
F27 - Buzzer operation mode:
Intra-range alarm
Extra-range alarm
[,,,0]
[,,,1]
F28 - Acting point of Buzzer by low temperature:
It is the minimun temperature to trigger the buzzer the configured Operation Mode of Buzzer [,F27].
F29 - Acting point of Buzzer by high temperature:
It is the superior value of temperature to the buzzer alarm act as the configured Operation Mode of
Buzzer [,F27].
F30 - Acting point of Buzzer by low humidity:
It is the inferior value of humidity to the buzzer alarm act as the configured Operation Mode of Buzzer
[,F27].
Acting point of Buzzer by high humidity:
[,F27]
F31 -
It is the superior value of humidity to the buzzer alarm act as the configured Operation Mode of Buzzer
.
F32 - Maximum time of the activated THERM output to activate the alarm:
Allows configuring the maximum time the output THERM can stay activated without reaching the
setpoint before activating the audible alarm (BUZZER). To deactivate this function, just decrement the
value until the message is displayed
Maximum time of the activated HUMID output to activate the alarm:
Allows configuring the maximum time the output HUMID can stay activated without reaching the setpoint
before activating the audible alarm (BUZZER). To deactivate this function, just decrement the value until
the message is displayed.
F34 - Maximum time of the activated AUX output to activate the alarm:
Allows configuring the maximum time the output AUX can stay activated without reaching the setpoint
before activating the audible alarm (BUZZER). To deactivate this function, just decrement the value until
the message is displayed.
F35 -Buzzer time on:
It is the time that the Buzzer will be turned on (cycle on). To turn it off the sonore alarm (Buzzer) adjust the
value “0” to this function.
F36 - Buzzer time off:
It is the time that the buzzer will be turned off (cycle off). To turn the sonore alarm (Buzzer) always on,
adjust the value “0” to this function.
F37 - Inhibition time of Buzzer during electrical supply:
It is the time were the alarm will kept turned off even if in alarm contitions.
It serves to inhibit the buzzer during the time while the system do not reaches the working control
temperature.
F38 - Output status in case of alarm:
Status output do not change in case of alarm
Turn off the output THERM, HUMID and AUX;
Note: The AUX output will not turn off if it is set to alarm output intra-or-extra range. In case of sensor
failure the outputs will be switched off independently of the parameter settled in that function.
[no,,] .
F33 -
[no,,]
[,,,0] ;
[,,,1]
[no,,]
F20 - AUX output (time on):
It is the time that AUX output will keep turned on when set to alarm or cyclical timer. See [,f14]
F21 - AUX output (time off):
It is the time that AUX output will keep turned off when set to alarm or cyclical timer. See [,f14].
F01 -
It is required for changing the configuration parameters. To visualize the adjusted parameters, it is not
necessary to insert this access code.
F02 -
[,,,0]Refrigeration
[,,,1]Heating
F03 - Minimum setpoint allowed to the end user (t
F04 - Maximum setpoint allowed to the end user (thermostat):
To prevent incorrect temperature setting.
F05 - Control differential (hysteresis) of the thermostat:
It is the difference of temperature (hysteresis) between ON and OFF the THERM output.
F06 - Minimum delay to turn the thermostat output on:
It is the minimum time that the thermostat will keep turned off, it means, the space of time between the
last stop and the next start.
F07- Humidistat operation mode (HUMID output):
F08 - Minimum setpoint allowed to the user (humidistat):
Access code: 123 (one hundred and twenty-three):
Thermostat operation mode (THERM output):
hermostat):
[,,,0]
[,,,1]
Dehumidification
Humidification
7.2.1 Parameters description
Seconds
Minutes
Seconds
Minutes
Seconds
Minutes
Minutes
Seconds
Value
Time on (F20) Time off (F21)
[
,,,0]
[,,,1]
[,,,2]
[,,,3]
Humidity display offset
-20.0
20.0
%RH
0
-20.0
20.0
0
%RH
[,F41]
= noLegend: [no,,]
Maximum time of the activated AUX output to activate the alarm
Buzzer time on
Buzzer time off
Inhibition time of Buzzer during electrical supply
Output status in case of alarm
Display mode
Temperature display offset
no
0
0
0
0
0
-5.0
999
999
999
999
1
2
5.0
min.
sec.
sec.
min.
-
-
°C
no
1
1
0
0
0
0
no
0
0
0
0
0
-9
999
999
999
999
1
2
9
no
1
1
0
0
0
0
min.
sec.
sec.
min.
-
-
°F
[,F34]
[,F35]
[,F36]
[,F37]
[,F38]
[,F39]
[,F40]
Acting point of Buzzer by low temperature
Acting point of Buzzer by high temperature
Acting point of Buzzer by low humidity
Acting point of Buzzer by high humidity
Maximum time of the activated THERM output to activate the alarm
Maximum time of the activated HUMID output to activate the alarm
-10.0
-10.0
0
0
no
no
70.0
70.0
100
100
999
999
°C
°C
%RH
%RH
min.
min.
-10.0
70.0
0
100
no
no
14
14
0
0
no
no
158
158
100
100
999
999
14
158
0
100
no
no
°F
°F
%RH
%RH
min.
min.
[,F28]
[,F29]
[,F30]
[,F31]
[,F32]
[,F33]