GASSONIC OBSERVER-i
63
See the ERROR OUTPUT Section for explanation of errors. Bit 13 is special for Modbus and HART.
When the Gassonic Observer-i is in acoustic test, this bit is set to “1” if the acoustic sound level is
above the desired level, and to “0” – if it is below the desired level. This allows the system to quickly
know if there is an acoustic test problem.
Bit 15 is set to “1” if any of the lower level faults are present. The system can now drill down and find
the root cause. Normally, this is not required at the system level, but only at a test station.
6.7.4. Fault Status/Error 2 (03H)
A read-only accessible register contains the bit map for any internal error that is present. The following
table shows the faults that are represented by each bit in the register.
Bit Position 15 14 13 12 11 10 9 8
Fault
Description
Word
3
Event
RAM
HART
RAM
System
RAM
Critical
RAM
Event
Flash
HART
Flash
System
Flash
Hex Value
0x8000 0x4000 0x2000 0x1000 0x0800 0x0400 0x0200 0x0100
Decimal Value
32768 16384 8192 4096 2048 1024 512 256
Display Fault
Code
N/A N/A N/A N/A N/A N/A N/A N/A
Bit Position 7 6 5 4 3 2 1 0
Fault
Description
Critical
Flash
CPU
RAM
CPU
Flash
-5V
Ref.
+5V
Ref.
-12V
Ref.
+12V
Ref.
Current
Ref.
Hex Value
0x0080 0x0040 0x0020 0x0010 0x0008 0x0004 0x0002 0x0001
Decimal Value
128 64 32 16 8 4 2 1
Display Fault
Code
N/A N/A N/A N/A N/A N/A N/A N/A
Table 15: Fault Status/Error 2
6.7.5. Model Type (04H)
A read returns the Decimal Value indicating the model number. The Gassonic Observer-i model
number is “6000”. Notice: If a newer Observer-i is designed to replace the Gassonic Observer-i the
model number will be different.
6.7.6. Software Revision Major (05H)
A read-only accessible register contains the major (user) alphanumeric revision value of the Gassonic
Observer-i embedded software expressed in 2 ASCII characters (REV “A” appears as a blank and the
letter A).
6.7.7. dB Level (06H)
A read-only accessible register contains the value of the measured SPL expressed in decibels.
6.7.8. Peak Sound (07H)
A read-only accessible register contains the acoustic test peak sound level expressed in decibels.