Default event codes
E.2 FireShield Technical Reference Manual
Default (4/2) event codes
Code Description
1<N> Fire alarm activation events
2<N> Waterflow alarm activation events
3<N> Supervisory signal activation events
4 Not used
5<N> Monitor signal activation events
6<N:1-4> NAC trouble activation events
65 Aux power trouble activation
66 Ground fault activation
67 DACT delivery trouble
68 DACT line 1fail
69 AC loss
6A Transformer 2 trouble
6B Charger trouble
6C Battery missing/Battery bad
6D FSRSI, FSRZI, FSRRM trouble
6E DACT line 2 fail
6F DACT abnormal test
7<N> IDC trouble activation
8<N> IDC disabled (not configurable)
9<N> IDC enabled (not configurable)
A<N:1-4> NAC disabled (not configurable)
A5 FSRRM outputs disabled (not configurable)
AA Internal communication trouble
AB Panel reset
AC Signal silence activated
AD Drill activated
AE DACT disabled
AF Walk test activated
B<N:1-4> NAC enabled (not configurable)
B5 FSRRM outputs enabled (not configurable)
BB Panel reset restore (not configurable)
BC Signal silence ended (not configurable)
BD Drill ended (not configurable)
BE DACT enabled (not configurable)
BF Walk test ended (not configurable)
C1 Program mode entry
C2 Program mode exit (not configurable)
CA Panel silence activated
D<N:1-4> NAC trouble restoration
D5 Aux power trouble restoration
D6 Ground fault restoration
D7 DACT delivery trouble restore
D8 DACT line 1 restoration
D9 AC loss restoration
DA Transformer 2 restoration
DB Charger trouble restoration
DC Battery missing/Battery bad restore
DD FSRSI, FSRZI, FSRRM restoration
DE DACT line 2 restoration
DF DACT normal test
E<N> Fire alarm restoration
E<N> Waterflow alarm restoration
Code Description
E<N> Supervisory restoration
E<N> Monitor restoration
F<N> IDC trouble restoration
Note: N is the circuit number.