11-94 SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES
4 115200 baud 115200 baud
FC102 unsigned 16 bits RS 485 Parity
0 None None
1OddOdd
2EvenEven
FC103 unsigned 16 bits Off / On Selection
0 Off Off
1OnOn
FC103A unsigned 16 bits No / Yes Selection
0NONO
1YESYES
FC104 unsigned 16 bits Ground CT Type
0 1 A Secondary 1 A Secondary
1 5 A Secondary 5 A Secondary
2 50:0.025 50:0.025
FC105 unsigned 16 bits Differential CT Type
0 None None
1 1 A Secondary 1 A Secondary
2 5 A Secondary 5 A Secondary
3 Direct Connect Direct Connect
FC106 unsigned 16 bits Voltage Transformer Connection Type
FC107 unsigned 16 bits Supply Frequency
0 60 Hz 60 Hz
1 50 Hz 50 Hz
FC108 unsigned 16 bits 61850 Status
0 Not Ready Not Ready
1ReadyReady
2 Default CID Default CID
FC109 unsigned 16 bits Flex Logic Status
0OKOK
1 Unknown Token Unknown Token
2 TooMany Latches Too Many Latches
3 TooMany Timers Too Many Timers
4 TooMany + OneShots Too Many + One Shots
5 TooMany - OneShots Too Many - One Shots
6 TooMany Duel1Shots Too Many Duel One Shots
7 Stack Overflow Stack Overflow
8 Stack Underflow Stack Underflow
9 Program Too Long Program Too Long
FC111 unsigned 16 bits Trip Relays
0TripTrip
1AlarmAlarm
FC112 unsigned 16 bits Communication Status
0 Error Error
1OKOK
FC115 unsigned 16 bits Alarm Type Selection
0 Off Off
Code Type Definition Long Description