11-160 SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
345 FORMAT CODES CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES
0ANDAND
1LATCHLATCH
FC150 unsigned 32 bits IP Address
FC155 unsigned 16 bits Profibus Baud Rate
0x0001 9600 9600
0x0002 19200 19200
0x0004 31250 31250
0x0008 45450 45450
0x0010 93750 93750
0x0020 187500 187500
0x0040 500000 500000
0x0080 1500000 1500000
0x07E2 Auto Detect Auto Detect
FC156 unsigned 16 bits DeviceNet Baud Rate
0 125 kbps 125 kbps
1 250 kbps 250 kbps
2 500 kbps 500 kbps
FC157 unsigned 16 bits LED Colour
0 Off Off
1RedRed
2GreenGreen
3 Orange Orange
FC157A unsigned 16 bits LED Colour (Subset A)
0 None None
1RedRed
2GreenGreen
FC160 unsigned 16 bits Auto/Manual Mode
0 Auto Auto
1 Manual Manual
FC167 unsigned 32 bits Contact/Virtual Input/Output Status
FC168 unsigned 32 bits Contact/Virtual Input/Output Status
FC169 unsigned 16 bits Month
0 Not Set Not Set
1 January January
2 February February
3MarchMarch
4 April April
5MayMay
6 June June
7 July July
8 August August
9 September September
10 October October
11 November November
12 December December
FC170 unsigned 16 bits Count of Week
0 Not Set Not Set