CHAPTER 11: 345 MODBUS MEMORY MAP AND FORMAT CODES 345 FORMAT CODES
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 11-163
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204C unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset C)
0x0000 Disabled Disabled
0x0041 Contact Input 2 Contact Input 2
FC204D unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset D)
0x0000 Disabled Disabled
0x0042 Contact Input 3 W2 Breaker 52a (CI#3)
FC204E unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset E)
0x0000 Disabled Disabled
0x0044 Contact Input 5 Contact Input 5
0x0045 Contact Input 6 Contact Input 6
0x0046 Contact Input 7 Contact Input 7
0x0047 Contact Input 8 Contact Input 8
0x0048 Contact Input 9 Contact Input 9
0x0049 Contact Input 10 Contact Input 10
FC204F unsigned 16 bits Contact Input FlexLogic Bit Field Values
(Subset F)
0x0000 Disabled Disabled
0x0043 Contact Input 4 W2 Breaker 52b (CI#4)
FC205 unsigned 16 bits Element Type 1
0 Disabled Disabled
1AlarmAlarm
2 Latched Alarm Latched Alarm
3TripTrip
4 Control Control
FC206 unsigned 16 bits Element Type 2
0 Disabled Disabled
1AlarmAlarm
2 Latched Alarm Latched Alarm
FC207 unsigned 16 bits Element Type 3
0 Disabled Disabled
1AlarmAlarm
2 Latched Alarm Latched Alarm
3 Control Control
FC208 unsigned 16 bits Relay Operation (Failsafe Non-Failsafe)
0 Failsafe Failsafe
1 Non-Failsafe Non-Failsafe
FC212 unsigned 16 bits LCD Test Paint Color
0 None None
1RedRed
2 Green Green
3BlueBlue
Code Type Definition Long Description