12-12 SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES
30846 0x34D Sample Index + Trace
Memory Sample 127
-32767 32767 1 --- F4 0 1
30847 0x34E Sample Index + Trace
Memory Sample 128
-32767 32767 1 --- F4 0 1
STATUS BUFFER
30948 0x3B3 Alarm Status 3 0 0xFFFFFFFF 1 --- FC181 0 2
30950 0x3B5 Alarm Status 2 0 0xFFFFFFFF 1 --- FC180 0 2
30952 0x3B7 Alarm Status 1 0 0xFFFFFFFF 1 --- FC179 0 2
30956 0x3BB Trip Status 3 0 0xFFFFFFFF 1 --- FC185 0 2
30958 0x3BD Trip Status 2 0 0xFFFFFFFF 1 --- FC184 0 2
30960 0x3BF Trip Status 1 0 0xFFFFFFFF 1 --- FC183 0 2
30966 0x3C5 Message Status 2 0 0xFFFFFFFF 1 --- FC188 0 2
30968 0x3C7 Message Status 1 0 0xFFFFFFFF 1 --- FC187 0 2
30970 0x3C9 Control Element Status 4 0 0xFFFFFFFF 1 --- FC194 0 2
30972 0x3CB Control Element Status 3 0 0xFFFFFFFF 1 --- FC193 0 2
30974 0x3CD Control Element Status 2 0 0xFFFFFFFF 1 --- FC192 0 2
30976 0x3CF Control Element Status 1 0 0xFFFFFFFF 1 --- FC191 0 2
30980 0x3D3 Block Status 3 0 0xFFFFFFFF 1 --- FC202 0 2
30982 0x3D5 Block Status 2 0 0xFFFFFFFF 1 --- FC201 0 2
30984 0x3D7 Block Status 1 0 0xFFFFFFFF 1 --- FC200 0 2
61850 STATUS
31510 0x5E5 61850 Status 0 2 1 --- FC108 0 1
31511 0x5E6 61850 N.V. Status 0 4 1 --- FC434 0 1
IEC61850 GOOSE STATUS
31515 0x5EA Remote GOOSE Status 0 0xFFFFFFFF 1 --- FC215 0 2
31517 0x5EC Remote GOOSE Header
Status
0 0xFFFFFFFF 1 --- FC215 0 2
THERMAL MODEL TRIP STATUS
31521 0x5F0 Trip Phase A Status 1 0 65535 1 --- FC134 0 1
31522 0x5F1 Trip Phase B Status 1 0 65535 1 --- FC134 0 1
31523 0x5F2 Trip Phase C Status 1 0 65535 1 --- FC134 0 1
PHASE IOC1 TRIP STATUS
31524 0x5F3 Trip Phase A Status 2 0 65535 1 --- FC134 0 1
31525 0x5F4 Trip Phase B Status 2 0 65535 1 --- FC134 0 1
31526 0x5F5 Trip Phase C Status 2 0 65535 1 --- FC134 0 1
PHASE TOC1 TRIP STATUS
31527 0x5F6 Trip Phase A Status 3 0 65535 1 --- FC134 0 1
31528 0x5F7 Trip Phase B Status 3 0 65535 1 --- FC134 0 1
31529 0x5F8 Trip Phase C Status 3 0 65535 1 --- FC134 0 1
PHASE IOC2 TRIP STATUS
31530 0x5F9 Trip Phase A Status 4 0 65535 1 --- FC134 0 1
31531 0x5FA Trip Phase B Status 4 0 65535 1 --- FC134 0 1
31532 0x5FB Trip Phase C Status 4 0 65535 1 --- FC134 0 1
PHASE OV TRIP STATUS
31533 0x5FC Trip Phase A Status 5 0 65535 1 --- FC134 0 1
31534 0x5FD Trip Phase B Status 5 0 65535 1 --- FC134 0 1
31535 0x5FE Trip Phase C Status 5 0 65535 1 --- FC134 0 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
words

Table of Contents