12-28 SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
350 MODBUS MEMORY MAP CHAPTER 12: 350 MODBUS MEMORY MAP AND FORMAT CODES
41570 0x621 LED 1 Source 0 0xFFFF 1 --- FC134B 0 1
41572 0x623 LED 2 Source 0 0xFFFF 1 --- FC134B 0 1
41574 0x625 LED 3 Source 0 0xFFFF 1 --- FC134B 0 1
41576 0x627 LED 4 Source 0 0xFFFF 1 --- FC134B 0 1
41578 0x629 LED 5 Source 0 0xFFFF 1 --- FC134B 0 1
41579 0x62A LED 5 Color 0 3 1 --- FC157 3 1
41580 0x62B LED 6 Source 0 0xFFFF 1 --- FC134B 0 1
41581 0x62C LED 6 Color 0 3 1 --- FC157 3 1
41582 0x62D LED 7 Source 0 0xFFFF 1 --- FC134B 0 1
41583 0x62E LED 7 Color 0 3 1 --- FC157 3 1
41584 0x62F LED 8 Source 0 0xFFFF 1 --- FC134B 0 1
41585 0x630 LED 8 Color 0 3 1 --- FC157 3 1
BREAKER TRIP COUNTER
42210 0x8A1 Breaker Trip Counter Initial
Trips
0 10000 1 --- F1 0 1
42211 0x8A2 Breaker Trip Counter
Function
0 2 1 --- FC206 0 1
42212 0x8A3 Breaker Trip Counter Limit 1 10000 1 trips F1 1 1
42213 0x8A4 Breaker Trip Counter Relay 0 0x7F 1 --- FC198 0 1
COIL MONITORS
42214 0x8A5 Bypass Breaker Status 0 1 1 --- FC126 0 1
TRIP COIL
42215 0x8A6 Relay1 Coil Monitor Function 0 2 1 --- FC206 0 1
42216 0x8A7 Relay1 Coil Monitor Pickup 1 10 1 s F1 5 1
42217 0x8A8 Relay1 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1
42218 0x8A9 Bypass Breaker Status 0 1 1 --- FC126 0 1
CLOSE COIL
42219 0x8AA Relay2 Coil Monitor Function 0 2 1 --- FC206 0 1
42220 0x8AB Relay2 Coil Monitor Pickup 1 10 1 s F1 5 1
42221 0x8AC Relay2 Coil Monitor Relay 0 0x7F 1 --- FC198 0 1
RELAY 1 TRIP
42222 0x8AD Relay 1 Seal-In 0 999 1 s F3 4 1
RELAY 2 CLOSE
42223 0x8AE Relay 2 Seal-In 0 999 1 s F3 4 1
USER CURVE
42241 0x8C0 User Curve A Parameter 0 1250000 1 s F27 500 2
42243 0x8C2 User Curve B Parameter 0 30000 1 s F27 0 2
42245 0x8C4 User Curve P Parameter 0 30000 1 --- F27 400 2
42247 0x8C6 User Curve Q Parameter 0 20000 1 --- F27 10000 2
42249 0x8C8 User Curve K Parameter 0 1999 1 s F23 0 1
COLD LOAD PICKUP
42225 0x8B0 Cold Load Pickup Function 0 2 1 --- FC206 0 1
42226 0x8B1 Cold Load Pickup Block Time 1 1000 1 s F1 5 1
42227 0x8B2 Outage Time before Cold
Load Pickup
1 1000 1 min F1 20 1
42228 0x8B3 External Cold Load Pickup
Initiate
0 0xEF02 1 --- F89 0 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
words