3-28 SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
IEC60870-5-104 PROTOCOL CHAPTER 3: ETHERNET INTERFACE
Group 16.
Global.
3.7. Clock synchronization:
Clock synchronization (optional, see Clause 7.6).
Day of week used.
RESI, GEN (time tag substituted/not substituted)
SU-bit (summertime) used.
3.8. Command transmission:
Direct command transmission.
Direct setpoint command transmission.
Select and execute command.
Select and execute setpoint command.
C_SE ACTTERM used.
No additional definition.
Short pulse duration (duration determined by a system parameter in the
outstation).
Long pulse duration (duration determined by a system parameter in the
outstation).
Persistent output.
Supervision of maximum delay in command direction of commands and
setpoint commands.
Maximum allowable delay of commands and setpoint commands: 5 s.
3.9. Transmission of integrated totals:
Mode A: Local freeze with spontaneous transmission.
Mode B: Local freeze with counter interrogation.
Mode C: Freeze and transmit by counter-interrogation commands.
Mode D: Freeze by counter-interrogation command, frozen values reported
simultaneously.
Counter read.
Counter freeze without reset.
Counter freeze with reset.
Counter reset.
General request counter.
Request counter group 1.
Request counter group 2.
Request counter group 3.
Request counter group 4.
3.10. Parameter loading:
Threshold value.
Smoothing factor.
Low limit for transmission of measured values.
High limit for transmission of measured values.
3.11. Parameter activation:
Activation/deactivation of persistent cyclic or periodic transmission of the
addressed object.
3.12. Test procedure:
Test procedure.
3.13. File transfer in monitor direction: