A–34 3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
MICS
3.1.3 Protection activation information (ACT)
ACT_0
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
phsA Boolean ST dchg O
phsB Boolean ST dchg O
phsC Boolean ST dchg O
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O
ACT_1
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
neut Boolean ST dchg O
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O
ACT_2
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O
ACT_3
Attribute Name Attribute Type FC TrgOp Value/Value Range M/O/C/E
DataAttribute
control and status
general Boolean ST dchg M
q Bvstring13 ST qchg M
t Utctime ST M
configuration, description and extension
d Vstring255 DC O
dataNs Vstring255 EX GE Multilin SR3
Namespace:2003
AC_DLN_M

Table of Contents