Modifications reserved Page 70/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
3. Disconnect on all Units the Battery from the UPS by opening (Pos. O) the External Battery
Switch or Fuses.
Wait 5 minutes for DC-Link Capacitors discharge.
4. Disconnect the Utility supply on all Units.
Complete power shutdown will OFF the LCD Display Panel.
Synoptic Diagram of first unit Synoptic Diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.