4 - 38 750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 4: MODBUS MEMORY MAP
1989 Breaker Operation Relays --- --- F57 None
198A Breaker Operation Delay 0.03 to 1.00 s F3 0.10 s
COIL MONITOR 1 (read/write setpoints)
1990 Coil Monitor 1 Function --- --- F38 Disabled
1991 Coil Monitor 1 Relays --- --- F57 None
1992 Breaker State Bypass --- --- F30 Disabled
1993
8
Coil Monitor 1 Delay 5 to 100 s F1 5 s
1994
8
Coil Monitor 1 Type --- --- F90 Trip
COIL MONITOR 2 (read/write setpoints)
1998 Coil Monitor 2 Function --- --- F38 Disabled
1999 Coil Monitor 2 Relays --- --- F57 None
199A Breaker State Bypass --- --- F30 Disabled
199B
8
Coil Monitor 2 Delay 5 to 100 s F1 5 s
199C
8
Coil Monitor 2 Type --- --- F90 Close
COIL MONITOR NAMES (read/write setpoints)
8
19A0
8
Coil Monitor 1 Name (9 registers) --- --- F33 Trip Coil Monitor
19A9
8
Coil Monitor 2 Name (9 registers) --- --- F33 Close Coil Monitor
ANALOG INPUT THRESHOLD NAMES (read/write setpoints)
8
19B2
8
Analog Input Threshold 1 Name (9 registers) --- --- F33 Analog Threshld 1
19BB
8
Analog Input Threshold 2 Name (9 registers) --- --- F33 Analog Threshld 2
FORCE OUTPUT RELAYS (read/write setpoints)
1A00 Force Output Relays Function --- --- F30 Disabled
1A01 Force 1 TRIP Relay --- --- F34 De-energized
1A02 Force 2 CLOSE Relay --- --- F34 De-energized
1A03 Force 3 ALARM Relay --- --- F34 De-energized
1A04 Force 4 AUXILIARY Relay --- --- F34 De-energized
1A05 Force 5 AUXILIARY Relay --- --- F34 De-energized
1A06 Force 6 AUXILIARY Relay --- --- F34 De-energized
1A07 Force 7 AUXILIARY Relay --- --- F34 De-energized
1A08 Force 8 SELF-TEST WARNING Relay --- --- F34 De-energized
1A09 Force Solid State Output --- --- F34 De-energized
FORCE ANALOG OUTPUTS (read/write setpoints)
1A10 Force Analog Outputs Function --- --- F30 Disabled
1A11 Force Analog Output 1 0 to 100 % F1 0%
1A12 Force Analog Output 2 0 to 100 % F1 0%
1A13 Force Analog Output 3 0 to 100 % F1 0%
1A14 Force Analog Output 4 0 to 100 % F1 0%
1A15 Force Analog Output 5 0 to 100 % F1 0%
1A16 Force Analog Output 6 0 to 100 % F1 0%
1A17 Force Analog Output 7 0 to 100 % F1 0%
1A18 Force Analog Output 8 0 to 100 % F1 0%
PICKUP TEST (read/write setpoints)
1A20 Pickup Test Function --- --- F30 Disabled
1A21 Pickup Test Relays --- --- F57 None
SETPOINT GROUPS (read/write setpoints)
1B00 Active Setpoint Group --- --- F79 Group 1
1B01 Edit Setpoint Group --- --- F80 Active Group
1B02 Breaker Open Inhibit --- --- F30 Disabled
1B03 Overcurrent Pickup Inhibit --- --- F30 Disabled
1B04 Overvoltage Pickup Inhibit --- --- F30 Disabled
1B05 Undervoltage Pickup Inhibit --- --- F30 Disabled
Table 3: Modbus Memory Map (Sheet 33 of 40)
ADDR DESCRIPTION RANGE UNITS TYPE DEFAULT
1 2 3 4 5 6 7 8 9 10 11 12 13
For explanation of Table footnotes, see the Memory Map Notes at the end of this table.