13-3
Data subject to change without notice 7/07. © 2007 GE Drives
Name Analog I/O Interface Card
Type
Function
2 analog outputs (1 voltage output and 1 current output): 11 types of data can be output.
Specifications Input Analog signal input (3 points) 32 and 31, 22 and 21, C2 and 21.
Terminal 32: Voltage input (both sides): 0 to ±10 VDC / 0 to ±100%, input impedance: 22k ohm.
Terminal 22: Voltage input (both sides): 0 to +10 VDC / 0 to +100%, input impedance: 22k ohm.
Terminal C2: Current input: 4 to + 20mADC / 0 to +100%, input impedance: 250k ohm.
For voltage input, power supply terminal for variable resistor (P10) should be connected.
Related function code o22
Output Analog signal input (2 points) between AO+ and AO-, CS+ and CS-
Terminal AO+: Voltage output: 0 to ±10 VDC, for max. 2 voltmeters, input impedance: 10k ohm
Terminal AO-: Voltage output common.
Terminal CS+: Current output: 4 to 20mAdc, max. 500 ohm
Terminal CS-: Current output common
(Terminal CS- is isloated from terminal 21, 31 and AO-)
Related function code o23
Connection
diagram
Remarks
3 analog inputs (2 voltage inputs and 1 current input): Torque limiting value (driving, braking), frquency setting, ratio setting
can be input respectively.
OPCG11SAIO
X9
X8
X7
X6
X5
X4
X3
X2
X1
E(G)
SD
DX
DX
FM
FM
CM
CM
REV
FW
PLC
CM
AO-
AO+
C2
21
22
31
32
Y1
Y2
Y3
Y4
Y5C
Y5A
C1
11
12
13
30C
30B
30A
(T0) *
AF-300
P11
MCCB
or
ELCB
* Terminals [R0] and [ T0] are no t provided f or 1.0 HP o r s m a ll e r.
RUN command
input
(R0) *
M
U
V
W
L3/T
L2/S
L1/R
CS+
CS-
(+)
(- )
(+)
VR
VR
(
1k
ohm)
(1k ohm)
Voltage input
(Single polarity)
Voltage input
(Both polarity)
Current input
Analog voltmeter
Anammeter