4-6
Data subject to change without notice 7/07. © 2007 GE Drives
The function code consists of alphanumeric characters with unique letters assigned to each function group.
Table 4-3-1
Function Code Function Remarks
F00 - F42 Fundamental functions
E01 - E47 Terminal Extension Functions
C01 - C33 Frequency Control Functions
P01 - P09 Motor Parameters
H03 - H39 High Performance Functions
A01 - A18 Alternative Motor Parameters
o01 - o29 Optional Functions Can only be selected with an option connected
To scroll the Function Select screen rapidly, use + or + to move the screen as a unit sorted
alphabetically.
Select the desired function and press
FUNC
DATA
to switch to the Data Setting screen.
On the Data Setting screen, the data values on the LCD can be increased or decreased in the smallest possible unit by
pressing
or . Holding down or causes the values to increase or decrease more rapidly. Other-
wise, select the digit to be modified using and then set data directly. When data is modified, the value before
modification will be displayed at the same time for reference purpose. To save the data, press
FUNC
DATA
. Pressing cancels
the changes made and returns control to the Function Select screen. The modified data will be effective in inverter
operation after the data has been saved by
FUNC
DATA
. If the data is not saved, there is no change to the inverter operation.
When data setting is disabled in the case of “Data protected” or “Data setting invalid during inverter running,” make the
necessary changes as indicated in Table 4-3-2 below.
Table 4.3.2
Display Reason for No Modification Release Method
LINK ACTIVE Currently writing from RS-485 / RTU option to
function is being made
Send a cancel command to function writing from RS-
485 RTU. Stops a “write” operation from the link
communication option.
NO SIGNAL(WE) The edit enabling command function is selected
using a general-purpose input terminal
For functions E01 to E09, turn data terminal 19 (edit
enabling command selection) ON
DATA PRTCTD Data protection is selected for function F00. Change function F00 to 0
INV RUNNING An attempt was made to change a function that
cannot be chan
g
ed durin
g
inverter o
p
eration.
Stop inverter operation
FWD/REV ON An attempt was made to change a function that
cannot be changed with the FWD/REV command
on.
Turn FWD/REV command off
F00 DATA PRTC
F01 FREQ CMD 1
F02 OPR METHOD
F03 MAX Hz-1
F00 DATA PRTC
F01 FREQ CMD 1
F02 PPR METHOD
F03 MAX Hz-1
F42 TRQ VECTOR 1
E01 X1 FUNC
E02 X2 FUNC
E03 X3 FUNC
A18 SLIP COMP 2
F00 DATA PRTC
F01 DATA PRTC
F02 OPR METHOD
+
+