EasyManua.ls Logo

GE AV-Line - Installation Details and Operational Guidelines; Bolting and Electrical Clearances; Ambient Temperatures and Short Circuits; Switchboard Maintenance

GE AV-Line
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GROUND
FAULT
PROTECTION
When
ground
fault
protection
is
furnished
,
it
is
important
that
all
field
connections
shall
be
made
correctly
so
that
the
ground
fault
protection
system
will
function
properly
.
Observe
the
following
rules
,
illustrated
in
Figs
.
12
,
13
.
ELECTRICAL
CLEARANCES
BOLTING
The
following
minimum
clearances
should
be
maintained
except
at
terminals
of
circuit
breakers
and
switches
:
AV
-
Line
switchboards
are
furnished
with
medium
carbon
steel
hardware
having
a
high
tensile
strength
.
V
4
"
to
Vs
"
bolts
have
a
tensile
strength
of
120
,
000
psi
,
and
W
to
5
/
s
"
bolts
have
a
strength
of
60
,
000
psi
.
Similar
hardware
should
be
used
for
any
additional
bolting
.
The
use
of
a
torque
wrench
is
recommended
to
assure
the
following
torques
.
These
torques
apply
to
alumi
-
num
or
copper
connections
.
When
torquing
bolts
the
following
values
are
nominal
:
0
-
125
V
126
-
250
V
251
-
600
V
Between
live
parts
of
opposite
polarity
:
Through
air
Over
surface
Between
live
parts
and
grounded
metal
through
air
or
over
surface
GROUNDING
Where
required
,
the
ground
bus
is
bolted
to
the
uprights
of
the
rear
frame
structure
.
It
is
arranged
so
that
connections
to
the
station
ground
can
be
made
in
any
unit
.
A
ground
lug
is
included
in
each
complete
equipment
for
tying
the
switchboard
to
the
station
ground
.
IT
IS
VERY
IMPORTANT
THAT
THE
EQUIPMENT
BE
ADEQUATELY
GROUNDED
,
TO
INSURE
THAT
ALL
PARTS
OF
THE
EQUIPMENT
,
OTHER
THAN
LIVE
PARTS
,
ARE
AT
GROUND
POTENTIAL
.
Ground
sensor
relays
are
recommended
for
protection
of
the
switchboard
.
V
2
"
3
/
4
"
1
"
2
"
3
/
4
"
11
/
4
"
8
-
10
lb
.
ft
.
16
-
19
lb
.
ft
.
23
-
27
lb
.
ft
.
35
-
40
lb
.
ft
.
45
-
50
lb
.
ft
.
1
/
4
"
20
bolts
5
/
i
6
w
18
bolts
16
bolts
1
/
2
"
13
bolts
s
/
s
"
16
bolts
Flat
washers
and
spring
washers
should
be
used
for
all
connec
-
tions
.
Washers
should
not
be
included
under
the
heads
of
car
-
riage
bolts
.
V
2
"
V
2
"
1
"
Switchboard
Maintenance
CAUTION
!
De
-
energize
this
equipment
before
performing
any
work
.
A
periodic
maintenance
schedule
should
be
established
to
ob
-
tain
the
best
service
from
the
switchboard
.
An
annual
check
and
overall
maintenance
procedure
for
the
switchboard
devices
and
all
connections
,
should
be
followed
as
a
minimum
requirement
.
Equipment
subject
to
highly
repetitive
operation
may
require
more
frequent
maintenance
.
A
permanent
record
of
all
maintenance
work
should
be
kept
.
The
record
should
include
a
list
of
periodic
checks
and
tests
made
,
the
date
they
were
made
,
the
condition
of
the
equipment
,
and
any
repairs
or
adjustments
that
were
performed
.
Maintenance
employees
should
follow
all
recognized
safety
practices
,
such
as
those
contained
in
the
National
Electrical
Code
,
OSHA
and
in
company
or
other
safety
regulations
during
maintenance
.
For
specific
information
regarding
the
maintenance
of
devices
,
such
as
circuit
breakers
,
relays
,
meters
,
etc
.
,
refer
to
the
sepa
-
rate
instruction
book
furnished
for
each
device
.
1
.
Periodically
inspect
switchboard
,
while
under
load
to
deter
-
mine
if
there
is
any
indication
of
overheating
.
If
overheating
or
any
other
unsatisfactory
condition
is
found
,
completely
de
-
energize
switchboard
and
investigate
.
Particularly
look
for
loose
bolts
and
connections
,
or
overloading
.
Remove
any
accumulation
of
dirt
or
other
foreign
matter
in
enclosure
.
Do
not
touch
live
parts
while
switchboard
is
energized
.
2
.
Plated
parts
may
become
dark
over
a
period
of
time
due
to
oxidation
.
Do
NOT
remove
this
discoloration
,
as
it
will
reduce
the
thickness
of
the
plating
.
3
.
Retighten
lugs
and
joints
to
eliminate
possible
heating
points
.
Transmittal
of
vibration
through
building
structure
and
conduit
to
switchboard
may
loosen
lugs
and
joints
.
Turning
load
off
and
on
causes
expansion
and
contraction
between
lug
and
cable
tending
to
loosen
lug
.
4
.
Do
not
open
sealed
breaker
or
trip
units
as
calibration
may
be
disturbed
.
Return
to
factory
for
any
replacement
.
AMBIENT
TEMPERATURES
AND
CIRCUIT
LOADING
Switchboards
are
designed
for
installation
where
average
ambi
-
ent
temperature
will
not
exceed
40
°
C
(
104
°
F
)
.
For
higher
tem
-
peratures
,
derating
may
be
required
.
The
conductor
temperatures
within
the
enclosure
may
be
as
high
as
80
°
C
(
176
°
F
)
.
Some
parts
of
breakers
,
switches
and
fuses
may
run
hotter
.
In
accordance
with
NEC
Art
.
384
-
16
(
c
)
it
is
recommended
that
thermal
-
magnetic
molded
-
case
breakers
in
switchboards
not
be
loaded
in
excess
of
80
%
of
rating
where
load
will
continue
for
three
hours
or
more
,
even
with
ambient
-
compensated
breakers
.
SHORT
CIRCUITS
Normally
,
the
overcurrent
protective
device
on
the
circuit
will
prevent
any
electrical
damage
except
at
the
actual
point
of
short
-
circuit
.
A
thorough
inspection
of
the
entire
system
after
any
large
fault
current
should
be
made
to
insure
that
there
has
been
no
mechanical
damage
to
conductors
,
insulation
or
equipment
.
In
addition
,
the
individual
overcurrent
protective
device
or
de
-
vices
which
performed
the
short
-
circuit
interruption
must
be
in
-
spected
for
possible
arcing
damage
to
contacts
,
arc
chutes
and
/
or
insulation
.
Do
not
open
sealed
devices
such
as
breaker
trip
units
or
150
A
frame
breakers
.
If
there
is
any
possibility
that
sealed
units
may
have
been
damaged
,
they
should
be
replaced
.
For
additional
details
on
the
particular
device
involved
,
refer
to
the
applicable
individual
instruction
book
.
ARCING
DAMAGE
TO
INSULATION
Some
organic
insulating
materials
carbonize
when
subjected
to
the
heat
of
an
electrical
arc
and
lose
their
insulating
qualities
.
Any
insulation
found
to
be
carbon
-
tracked
must
be
replaced
before
applying
power
.
(
Continued
on
Page
12
)
11
Courtesy of NationalSwitchgear.com

Related product manuals