EasyManua.ls Logo

GE AV-Line - Cable Bracing and Installation; Cable Bracing Requirements; Main Cable Installation (AV-1;2;5)

GE AV-Line
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WARNING
:
Short
Circuit
Cable
Bracing
Required
s
:
\
LOAD
CABLE
BRACING
MAIN
CABLE
BRACING
Load
cable
short
circuit
bracing
is
required
for
each
component
installed
in
an
AV
-
3
or
AV
-
4
switchboard
section
with
available
short
circuit
currents
of
65
,
000
rms
symmetrical
amperes
and
above
.
Main
cable
bracing
is
required
when
five
cables
per
phase
or
less
feed
a
switchboard
at
available
short
circuit
currents
of
100
,
000
and
150
,
000
rms
symmetrical
amperes
,
and
eight
cables
per
phase
or
less
at
an
available
short
circuit
current
of
200
,
000
rms
symmetrical
amperes
.
Assembly
,
purchasing
and
maintenance
instructions
for
main
cable
short
circuit
bracing
can
be
found
on
pages
6
and
7
.
Assembly
,
purchasing
and
maintenance
instructions
for
load
cable
short
circuit
bracing
can
be
found
on
page
8
.
Installing
The
Main
Cable
AV
-
1
,
AV
-
2
AND
AV
-
5
SWITCHBOARDS
UTILIZING
CORD
FOR
SHORT
CIRCUIT
PROTECTION
PRIOR
TO
INSTALLATION
minimum
,
making
6
revolutions
around
the
"
A
and
B
,
?
phase
main
cables
and
6
revolutions
around
the
B
"
and
C
phase
main
cables
.
Now
,
with
the
remaining
cord
,
wrap
the
main
cable
lashing
to
the
cable
braces
in
between
phases
with
4
to
5
revolu
-
tions
,
tieing
a
knot
to
the
cable
braces
as
you
complete
your
last
revolution
.
All
revolutions
should
be
made
as
tight
as
possible
so
as
to
prevent
whipping
during
short
circuits
.
Before
any
installation
work
is
performed
,
study
all
drawings
furnished
by
the
General
Electric
Company
for
the
particular
installation
.
These
include
arrangement
drawings
(
front
,
end
and
plan
view
)
,
connection
diagrams
and
schedule
of
equip
-
ment
.
Any
material
external
to
the
equipment
which
may
be
required
to
meet
any
local
codes
(
railings
,
etc
.
)
is
not
furnished
.
INSPECTION
AFTER
MAIN
CABLE
INSTALLATION
CABLE
BRACE
4
To
prevent
heating
,
there
should
be
no
closed
loop
of
steel
around
a
single
conductor
or
group
of
conductors
which
does
not
include
all
the
conductors
(
including
the
neutral
)
of
the
circuit
.
If
the
conductors
must
pass
through
separate
holes
in
a
piece
of
steel
,
slots
should
be
cut
between
the
holes
.
Do
not
allow
cables
carrying
heavy
current
to
come
near
instruments
or
meters
as
this
may
affect
their
accuracy
.
Use
the
minimum
amount
of
cable
necessary
to
accomplish
the
connections
.
The
increased
resist
-
ance
of
longer
cables
generates
unnecessary
heat
.
Main
cable
lashing
should
be
checked
bi
-
monthly
.
-
3
)
f
s
f o l
[
s
-
i
-
MAIN
CABLE
TERMINALS
FIGURE
7
B
INSTALLATION
PROCEDURES
FOR
MAIN
CABLE
WITH
SHORT
CIRCUIT
PROTECTION
Align
conduit
holes
in
a
linear
orientation
directly
over
or
as
close
as
possible
to
the
braces
.
Consideration
should
be
given
to
installing
conduits
or
sleeves
which
might
be
required
for
future
connections
.
Run
and
bend
the
main
cable
in
a
most
convenient
orientation
,
making
sure
the
main
cable
has
been
located
directly
up
against
the
cable
braces
before
it
connects
to
the
main
cable
terminals
.
Lash
the
main
cable
according
to
Figure
7
B
above
,
using
a
polyester
braided
rope
having
a
tensile
strength
of
2000
lbs
.
)
6
Courtesy of NationalSwitchgear.com

Related product manuals