CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-83
2
" 6213 Autoreclose 1 Dead Time Shot 3 0 to 655.35 s 0.01 F001 300
" 6214 Autoreclose 1 Dead Time Shot 4 0 to 655.35 s 0.01 F001 400
" 6215 Autoreclose 1 Reset Lockout Delay 0 to 655.35 s 0.01 F001 6000
" 6216 Autoreclose 1 Reset Time 0 to 655.35 s 0.01 F001 6000
" 6217 Autoreclose 1 Incomplete Sequence Time 0 to 655.35 s 0.01 F001 500
" 6218 Autoreclose 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6219 Autoreclose 1 Reduce Max 1 0 to 4294967295 --- 1 F300 0
" 621B Autoreclose 1 Reduce Max 2 0 to 4294967295 --- 1 F300 0
" 621D Autoreclose 1 Reduce Max 3 0 to 4294967295 --- 1 F300 0
" 621F Autoreclose 1 Add Delay 1 0 to 4294967295 --- 1 F300 0
" 6221 Autoreclose 1 Delay 1 0 to 655.35 s 0.01 F001 0
" 6222 Autoreclose 1 Add Delay 2 0 to 4294967295 --- 1 F300 0
" 6224 Autoreclose 1 Delay 2 0 to 655.35 s 0.01 F001 0
" 6225 Reserved (4 items) 0 to 0.001 --- 0.001 F001 0
F35, F60, L30 6229 ...Repeated for Autoreclose 2
" 6252 ...Repeated for Autoreclose 3
F35, F60 627B ...Repeated for Autoreclose 4
F35 62A4 ...Repeated for Autoreclose 5
" 62CD ...Repeated for Autoreclose 6
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 or 3 Modules)
C70, D30, D60,
F35, F60, L30,
L60, L90, T60
6300 Negative Sequence Time Overcurrent 1
Function
0 to 1 --- 1 F102 0 (Disabled)
" 6301 Negative Sequence Time Overcurrent 1
Signal Source
0 to 5 --- 1 F167 0 (SRC 1)
" 6302 Negative Sequence Time Overcurrent 1
Pickup
0.02 to 30 pu 0.001 F001 1000
" 6303 Negative Sequence Time Overcurrent 1
Curve
0 to 16 --- 1 F103 0 (IEEE Mod
Inv)
" 6304 Negative Sequence Time Overcurrent 1
Multiplier
0 to 600 --- 0.01 F001 100
" 6305 Negative Sequence Time Overcurrent 1
Reset
0 to 1 --- 1 F104 0
(Instantaneo
us)
" 6306 Negative Sequence Time Overcurrent 1
Block
0 to 4294967295 --- 1 F300 0
" 6308 Negative Sequence Time Overcurrent 1
Target
0 to 2 --- 1 F109 0 (Self-reset)
" 6309 Negative Sequence Time Overcurrent 1
Events
0 to 1 --- 1 F102 0 (Disabled)
" 630A ...Repeated for Negative Sequence Time
Overcurrent 2
T60 6314 ...Repeated for Negative Sequence Time
Overcurrent 3
Capacitor Bank Overvoltage Settings (Read/Write Grouped Setting) (3 Modules)
C70 6330 Bank Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6331 Bank Phase Overvoltage 1 Bus Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6332 Bank Phase Overvoltage 1 Neutral Source 0 to 5 --- 1 F167 0 (SRC 1)
" 6333 Bank Phase Overvoltage 1 Bank Ground 0 to 2 --- 1 F093 0 (Grounded)
" 6334 Bank Phase Overvoltage 1 Curve 0 to 3 --- 1 F094 0 (FlexCurve
A)
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals