CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-111
2
" 7393 Disconnect Switch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 7394 Reserved --- --- --- F001 0
" 7395 ...Repeated for Disconnect Switch 2
" 73BA ...Repeated for Disconnect Switch 3
" 73DF ...Repeated for Disconnect Switch 4
" 7404 ...Repeated for Disconnect Switch 5
" 7429 ...Repeated for Disconnect Switch 6
" 744E ...Repeated for Disconnect Switch 7
" 7473 ...Repeated for Disconnect Switch 8
B30, C60, C70,
D60, F35, F60,
L90, N60, T35,
T60
7498 ...Repeated for Disconnect Switch 9
" 74BD ...Repeated for Disconnect Switch 10
" 74E2 ...Repeated for Disconnect Switch 11
" 7507 ...Repeated for Disconnect Switch 12
B30, C60, D60,
F35, F60, L90,
N60, T35, T60
752C ...Repeated for Disconnect Switch 13
" 7551 ...Repeated for Disconnect Switch 14
" 7576 ...Repeated for Disconnect Switch 15
" 759B ...Repeated for Disconnect Switch 16
B30, C60, F35,
L90, N60, T35,
T60
75C0 ...Repeated for Disconnect Switch 17
" 75E5 ...Repeated for Disconnect Switch 18
" 760A ...Repeated for Disconnect Switch 19
" 762F ...Repeated for Disconnect Switch 20
" 7654 ...Repeated for Disconnect Switch 21
" 7679 ...Repeated for Disconnect Switch 22
" 769E ...Repeated for Disconnect Switch 23
" 76C3 ...Repeated for Disconnect Switch 24
Instantaneous Overcurrent (Read/Write Grouped Setting) (24 Modules)
B90 7600 Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 7601 Instantaneous Overcurrent 1 CT 0 to 23 --- 1 F400 0
" 7602 Instantaneous Overcurrent 1 Pickup 0.005 to 30 pu 0.001 F001 1200
" 7603 Instantaneous Overcurrent 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
" 7604 Instantaneous Overcurrent 1 Reset Delay 0 to 65.535 s 0.001 F001 0
" 7605 Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
" 7607 Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7608 Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 7609 Reserved (2 items) 0 to 65535 --- 1 F001 0
" 760A ...Repeated for Instantaneous Overcurrent
2
" 7614 ...Repeated for Instantaneous Overcurrent
3
" 761E ...Repeated for Instantaneous Overcurrent
4
" 7628 ...Repeated for Instantaneous Overcurrent
5
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals