EasyManua.ls Logo

GE b30 - Page 168

GE b30
532 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-148 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
Pilot Permissive Overreach Transfer Trip (POTT) Settings (Read/Write)
L60 A070 POTT Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" A071 POTT Permissive Echo 0 to 1 --- 1 F102 0 (Disabled)
" A072 POTT Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" A073 POTT Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 20
" A074 POTT Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
" A075 POTT Echo Duration 0 to 65.535 s 0.001 F001 100
" A076 POTT Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 50
" A077 POTT Seal In Delay 0 to 65.535 s 0.001 F001 400
" A078 POTT Ground Direction OC Forward 0 to 4294967295 --- 1 F300 0
" A07A POTT Rx 0 to 4294967295 --- 1 F300 0
" A07C POTT Echo Lockout 0 to 65.535 s 0.001 F001 250
" A07D POTT Target 0 to 2 --- 1 F109 0 (Self-reset)
" A07E POTT Events 0 to 1 --- 1 F102 0 (Disabled)
VT Fuse Failure Settings (Read/Write) (2, 4, or 6 Modules)
C60, C70, D30,
D60, F35, F60,
G30, G60, L30,
L60, L90, M60,
N60, T60
A09A VT Fuse Failure Function 0 to 1 --- 1 F102 0 (Disabled)
" A09B VT Fuse Failure Neutral Wire Open Function 0 to 1 --- 1 F102 0 (Disabled)
" A09C VT Fuse Failure Neutral Wire Open 3rd
Harmonic Pickup
0.004 to 3 pu 0.001 F001 100
" A09D VT Fuse Failure 1 Alarm Delay 0 to 65.535 s 0.001 F001 1000
" A09E ...Repeated for Source 2
C60, C70, D60,
F35, F60, G30,
G60, L90, M60,
N60, T60
A0A2 ...Repeated for Source 3
" A0A6 ...Repeated for Source 4
C70, F35, N60,
T60
A0AA ...Repeated for Source 5
" A0AE ...Repeated for Source 6
VT Fuse Failure Actuals (Read Only) (2, 4, or 6 Modules)
C60, C70, D30,
D60, F35, F60,
G30, G60, L30,
L60, L90, M60,
N60, T60
A0B2 VTFF x V0 3rd harmonic 0 to 999999.999 V 0.001 F060 0
" A0B4 ...Repeated for Source 2
C60, C70, D60,
F35, F60, G30,
G60, L90, M60,
N60, T60
A0B6 ...Repeated for Source 3
" A0B8 ...Repeated for Source 4
C70, F35, N60,
T60
A0BA ...Repeated for Source 5
" A0BC ...Repeated for Source 6
Summator Settings (Read/Write Setting) (6 Modules)
N60 A0C0 Summator 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" A0C1 Summator 1 Input Mode 0 to 1 --- 1 F515 0 (SIGNED)
" A0C2 Summator 1 Hold 0 to 4294967295 --- 1 F300 0
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Related product manuals