CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-215
3
FltLoopRis MV D30, D60, L60, L90 - The fault loop resistance FltRFLO
FltMulti SPS Fault indication - Multi phase fault.
The PHASE SELECT MULTI-P operand.
PhSelGAPC
FltRis MV L90 - The fault resistance at the fault point FltRFLO
FltSegment ENS L90 - Indicates in which segment of the line the fault occurred: 0 = N/A, 1 = LOCAL,
2 = REMOTE 1, 3 = REMOTE 2
FltRFLO
FltSLG SPS Fault indication - single line to ground.
The PHASE SELECT SLG operand.
PhSelGAPC
FltVoid SPS Fault indication - Fault type not detected.
The PHASE SELECT VOID operand.
PhSelGAPC
FrcTrigger SPC Command for the Hi-Z Oscillography Force Trigger HiZPHIZ
FrstEthFail SPS First Ethernet failure.
The FIRST ETHERNET FAIL operand.
LPHD
Function1 ENG Function Enable/Disable setting: 0 = Disabled, 1 = Enabled (note that TISSUE 670
suggests something like this named SetMod)
Master/LLN0
FwdOp SPS Fault direction is forward.
The NEG SEQ DIR OC1 FWD operand.
The NTRL DIR OC1 FWD operand.
NegDocRDIR, NeuDocRDIR
GoDatSetRef ORG Expected value of datSet field in messages subscribed to by RxGOOSE#
The setting RxGOOSE1 DatSet.
LGOS
GoEnaPort1 ENG Enable all GOOSE on Ethernet port setting: 0 = Disabled, 1 = Enabled Master/LLN0
GoID VSG Expected value of goID field in messages subscribed to by RxGOOSE#
The setting RxGOOSE1 ID.
LGOS
GndAmp MV Ground current.
The FIELD GROUND CURRENT in amperes.
FldGnd0PHIZ
GndNeutInd SPS An LED.
The LED NEUTRAL/GROUND operand.
LEDsIHMI
GndRis MV Ground resistance.
FIELD GROUND RESIST in ohms.
STATOR GND. RESIST in kilo ohms.
FldGnd0PHIZ, SubHaPHIZ
GpsFail1 SPS GPS failed at terminal corresponding to instance number.
The 87L DIFF GPS 1 FAIL operand.
LinDfPDIF
GrAct1 SPS Setting group corresponding to index is active (not instantiated in C30).
The SETTING GROUP ACT 1 operand.
Master/LLN0
GrdMasterID VSS Grand master ID actual value TmClkLTMS
Ha3NV MV Third harmonic component of neutral voltage.
STATOR GND 3RD HARM VN in volts.
StatrPHIZ
Ha3ZroV MV Third harmonic component of zero sequence voltage.
STATOR GND 3RD HARM V0 in volts.
StatrPHIZ
HiZIOC ACT Indicates phase instantaneous overcurrent has operated HiZPHIZ
HiZSt ENS Represents the status of Hi-Z fault detection function HiZPHIZ
HzChgRte MV Frequency rate of change measured value.
FREQUENCY RATE OF CHANGE 1 in Hz/s.
RteHzPFRC
HzLedInd SPS An LED.
The LED FREQUENCY operand.
LEDsIHMI
HzObAccum MV FREQUENCY OOB BAND 1 ACCUMULATION in percentage (%) HzBnd$PTUF
IdFail1 SPS ID check for a peer L30/L90 on the channel has failed.
87L DIFF CH 1 ID FAIL operand, which becomes On when the differential element's
ID check for a peer L30 on channel 1 has failed.
LinDfPDIF
IndFailBeh ENG Setting to select the behavior of the RxGOOSE Boolean when the sending device is
offline: 0 = On, 1 = Off, 2 = Latest/On, 3 = Latest/Off
GGIO3
IndPos1 DPS Generic remote DPS input status values: 0 for intermediate-state, 1 for off, 2 for
on, 3 for bad-state.
RxGOOSE DPS1 actual value.
GGIO3
Data object
name
CDC Semantics Used in logical nodes…