CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-217
3
LocSetAcsOff SPS Indicates operations of FlexLogic operand ACCESS LOC SETG OFF SecGSAL
LocSetAcsOn SPS Indicates operations of FlexLogic operand ACCESS LOC SETG ON SecGSAL
LosLife MV XFMR LIFE LOST actual values LosLifSPTR
LosLifeRte MV DAILY RATE LOL actual values LosLifSPTR
LosPkt1 SPS The lost packet threshold has been exceeded.
The 87L DIFF CH 1 LOSTPKT operand, which becomes On when the differential
element has detected the lost packet threshold has been exceeded on channel 1.
LinDfPDIF
LossLd ACT The high impedance fault phase A, B, C loss of load element has operated HiZPHIZ
Lower SPS PID Lower operand. The PID 1 LOWER operand value. PIDRegFPID
MAC VSG Expected value of Destination MAC address field in messages subscribed to by
RxGOOSE#
LGOS
MajorErr SPS Any of the major self-test errors generated (major error).
The ANY MAJOR ERROR operand.
LPHD
ManMod SPS Capacitor control in manual mode.
The CAP 1 IN MAN operand.
CapCtlGAPC
MaxAsymOp1 SPS Asymmetry on the channel exceeded pre-set value.
The 87L DIFF CH 1 MAX ASYM operand, which becomes On when the Asymmetry
on channel 1 exceeded preset value.
LinDfPDIF
MaxCompHz MV The frequency of the learned maximum broken rotor bar spectral component.
MAXIMUM COMPONENT FREQ. in Hz.
BknRotSVBR
MaxCompLevel MV Indicates the learned maximum level of the broken rotor bar spectral component
since the last data clear.
MAXIMUM COMPONENT LEVEL in dB.
BknRotSVBR
MaxIntrA MV Indicates Breaker Arcing Current per phase.
BKR 1 AMP MAX phase A/B/C.
CBArcΘSCBR
MaxLoadDev MV Indicates the motor load standard deviation at the time when data for the
maximum broken rotor bar was acquired.
LOAD DEV. AT BRB MAX in x FLA.
BknRotSVBR
MaxMotLoad MV Indicates the average motor load at the time when data for the maximum broken
rotor bar was acquired.
MOTOR LOAD AT BRB MAX in x FLA.
BknRotSVBR
MaxVal1 ASG Maximum value in deadband calculations TDCInGGIO1,
TDCOutGGIO1
MinorErr SPS Any of the minor self-test errors generated (minor error).
The ANY MINOR ERROR operand.
LPHD
MinVal1 ASG Minimum value in deadband calculations TDCInGGIO1,
TDCOutGGIO1
MMSConnects MV Number of MMS client connections active LPHD
MnlCls SPS Manual close initiated.
The BREAKER 1 MNL CLS operand.
Bkr0XCBR
MnlOpn SPS Manual open initiated.
The BREAKER 1 MNL OPEN operand.
Bkr0XCBR
Month1 SPS Current month, where 1 = January.
The MONTH operand.
TmDayGAPC
MotLoad MV The average motor load at the time of the broken rotor bar data acquisition stage.
MOTOR LOAD AT BRB CALC. in x FLA
BknRotSVBR
MotStatus ENS Indicated the status of the motor (in Actual Values) where 0 = Offline, 1= Starting,
2 = Running and 3 = Overload.
Thermal Model MOTOR STATUS.
MotThmPTTR
MotUnb MV % thermal model motor unbalance.
THERMAL MODEL MOTOR UNBALANCE in percentage (%).
MotThmPTTR
NegTotVArh MV SRC 1 Total VAr-hour in negative direction EnrMtrMMTR
NegTotWh MV SRC 1 Total Watt-hour in negative direction EnrMtrMMTR
NeutOpn SPS Indicates source has lost voltage signal.
The SRC1 VT NEU WIRE OPEN operand.
VtffGAPC
Data object
name
CDC Semantics Used in logical nodes…