3-218 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
NeutSupn SPS Neutral overcurrent supervision status.
The GND DIST Z1 SUPN IN operand.
GndDisPDIS
NeutVx CMV Neutral point voltage in pu NuVUnPTOV
NumCycPer INS Number of cycles of the nominal frequency. The CYCLES PER RECORD actual
value.
OscRDRE
Off SPS Logic 0 fixed operand Master/LLN0
Offline SPS Indicate the motor is offline.
The MOTOR OFFLINE operand.
MotThmPTTR
On SPS Logic 1 fixed operand Master/LLN0
OnePoleOpn SPS One pole is open, others closed.
The BREAKER 1 ONE P OPEN operand.
Bkr0XCBR
OnePU ASG The per-unit base factor applied to the corresponding RxGOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity.
GGIO3
OpAlm ACT Operate indicates the alarm decision of a protection function.
The U/CURR ALARM OP operand.
The UNDERPWR 1 ALARM OP operand.
UnCurPTUC, UnPwrPDUP
OpBia ACT B90 Operate indicates the trip decision of a biased protection logic B_DifPDIF
OpHiSet ACT B90 Operate indicates the trip decision of the HISET element of breaker failure
current supervision function.
B_BFaiPIOC
OpLoSet ACT B90 Operate indicates the trip decision of the LOSET element of breaker failure
current supervision function.
B_BFaiPIOC
OpnCirc SPS Open circuit detected.
The RRTD RTD 1 OPEN operand.
The RTD Ip 1 OPEN operand.
PRTDsSTMP, RRTDsSTMP
OpnSt1 SPS Open status detected.
The BREAKER/SWITCH OPEN operand.
The RxGOOSE DPS1 Off operand.
BkrΘXCBR, Bkr0XCBR,
Disc0XSWI, DiscΘXSWI,
GGIO3
OpPhs1 SPS Indicates a trip decision for a particular cause per phase.
The BUS 1 BIASED OP A/B/C operand.
The BUS 1 UNBIASED OP A/B/C operand.
The PHS DIST Z1 OP AB/BC/CA operand.
BusDifPDIF, PhsDisPDIS
OpSig MV Operating signal, the analogue value used by the comparator.
FLEXELEMENT 1 OpSig, in per unit.
FlxElGAPC
OpUnBia ACT B90 Operate indicates the trip decision of an unbiased protection logic B_DifPDIF
OpV WYE Phase Operating Voltages.
Bank Operating Voltage in per unit for Phase A, B, and C.
CPhOvPTOV
OscilGOOSE SPS One or more of GGIO1.Ind###.stVal has been frozen due to frequent status
changes (chatter) in the mapped operand.
The Oscillatory GOOSE operand.
LPHD
OtherInd SPS An LED.
The LED OTHER operand.
LEDsIHMI
OvlTripTm MV Indicates estimation of trip time on overload.
The ESTIMATED TRIP TIME ON OVERLOAD in seconds.
MotThmPTTR
OutOfSrv SPS Out-of-service.
The BREAKER 1 OOS operand.
Bkr0XCBR
P1Rip SPS Autoreclose A single pole is in progress.
The AR 1-P RIP operand.
Rec13pRREC
P3Rip1 SPS Autoreclose 3-pole is in progress via dead time number indicated by the data
instance number.
The AR 3-P/1 RIP operand.
Rec13pRREC
P3Tr SPS Force any trip to 3-phase trip.
The AR FORCE 3-P TRIP operand.
Rec13pRREC
PFLLfail SPS Phase and/or frequency lock loop (PFLL) has failed.
The 87L DIFF PFLL FAIL operand, which becomes On when the differential
element's phase and frequency lock loop (PFLL) has failed.
LinDfPDIF
Data object
name
CDC Semantics Used in logical nodes…