CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-221
3
SntpFail SPS SNTP server is not responding.
The SNTP FAILURE operand.
LPHD
SPDTR SPS Motor switches from speed 2 to speed 1.
MOTOR SPD2 TR 2-1 OP operand.
S2AcTmPMSS
Spt MV Set point value. The PID 1 Setpoint value. PIDRegFPID
Start SPS One-second pulse at set time of day timer # start time.
The TIME OF DAY 1 START operand.
TmDayGAPC
Starting SPS Indicate the motor is starting.
The MOTOR STARTING operand.
MotThmPTTR
StlGMP SPS Indicates status of IGMP connection for R-GOOSE multicast reception.
The R-RxGOOSE1 IGMP On operand.
LGOS
Stop SPS One-second pulse at set time of day timer 1 stop time.
The TIME OF DAY 1 STOP operand.
TmDayGAPC
StrAccTm1 MV Indicates motor start acceleration time. START 1 ACCELERATION TIME in seconds. MAccTmPMSS
StrAlm ACD Indicates the detection of a fault or an unacceptable condition.
The RRTD RTD 1 ALARM PKP operand.
The RTD Ip 1 ALARM PKP operand.
The U/CURR ALARM PKP operand.
The UNDERPWR 1 ALARM PKP operand.
PRTDsSTMP, RRTDsSTMP, 
UnCurPTUC, UnPwrPDUP
StrBia ACD B90 Start Biased indicates the detection of a fault or an unacceptable condition 
by Biased Differential element
B_DifPDIF
StrCls SPS Close start indicates the pickup of close command, and its operation is pending.
The AVR 1 CLOSE PKP operands.
AvrGAPC
StrEffA1 MV Indicates motor start effective current.
START 1 EFFECTIVE CURRENT in x FLA.
MAccTmPMSS
StrHrLOTm MV Start/Hour Lockout Time in minutes StrRtePMRI
StrInd SPS An LED.
The LED PICKUP operand.
LEDsIHMI
StrOpn SPS Open start indicates the pickup of open command, and its operation is pending.
AVR 1 OPEN PKP operands.
AvrGAPC
StrOutgoing SPS This Data Object indicates an unstable Power swing detection for outgoing Locus.
The POWER SWING OUTGOING operand.
PwrSwgRPSB
StrPeak1 MV Indicates motor start peak current.
START 1 PEAK CURRENT in x FLA.
MAccTmPMSS
StrPhs1 SPS Indicates the detection of a fault or an unacceptable condition on a particular 
phase-to-phase loop.
The PHS DIST Z1 PKP AB/BC/CA operand in Phase-To-Phase.
PhsDisPDIS
StrRec3p SPS Initiate a three-pole reclose.
The TRIP AR INIT 3-POLE operand.
TrOutPTRC
StrTD1 INS Represents UTC timestamp for motor acceleration Time/DATE in seconds elapsed 
since 00:00:00, 1970/01/01.
The START 1 TIME/DATE actual value.
MAccTmPMSS
StrZ2GndDl SPS Start zone 2 ground timer.
The TRIP Z2GR TMR INIT operand.
TrOutPTRC
StrZ2PhDl SPS Start zone 2 phase timer.
The TRIP Z2PH TMR INIT operand.
TrOutPTRC
StubBusOp SPS The stub bus function is operated.
The STUB BUS OP operand, which becomes On when the Stub Bus function is 
active.
LinDfPDIF
SumHa3NVZroV MV Sum of third harmonic neutral voltage and zero sequence voltage.
The STATOR GND 3RD HARM VN+V0 in volts.
StatrPHIZ
SwFail SPS Autoreclose mode switching failed.
The AR MODE SWITCH FAIL operand.
Rec13pRREC
SysExcp SPS System exception.
The SYSTEM EXCEPTION operand.
LPHD
Data object
name
CDC Semantics Used in logical nodes…