CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-29
2
Subharmonic Stator Ground Actual Values (Read Only)
G60 1678 Subharmonic Injection Voltage 0 to 999999.999 V 0.001 F060 0
" 167A Subharmonic Injection Current 0 to 999999.999 A 0.001 F060 0
" 167C Stator Ground Resistance 0 to 500 kOhm 0.001 F003 500000
" 167E Stator Ground Resistance Exceeded 0 to 0.1 --- 0.1 F208 (none)
" 167F Subharmonic Injection Current Angle -360 to 360 --- 0.1 F002 0
Sensitive Directional Power Actual Values (Read Only) (2 Modules)
C60, D60, F60,
G30, G60, L90,
M60, N60, T60
1680 Sensitive Directional Power 1 Power -2147483647 to
2147483647
W1F0600
" 1682 Sensitive Directional Power 2 Power -2147483647 to
2147483647
W1F0600
Restricted Ground Fault Currents (Read Only) (4 or 6 Modules)
F60, G30, G60,
L90, T35, T60
16A0 Differential Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
" 16A2 Restricted Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
" 16A4 ...Repeated for Restricted Ground Fault 2
" 16A8 ...Repeated for Restricted Ground Fault 3
" 16AC ...Repeated for Restricted Ground Fault 4
T35, T60 16B0 ...Repeated for Restricted Ground Fault 5
" 16B4 ...Repeated for Restricted Ground Fault 6
Field Unit RTD Actuals (Read Only) (8 Modules)
All except B90,
L60
16C0 Field RTD 1 Value -32768 to 32767 °C 1 F002 0
" 16C1 ...Repeated for Field RTD 2
" 16C2 ...Repeated for Field RTD 3
" 16C3 ...Repeated for Field RTD 4
" 16C4 ...Repeated for Field RTD 5
" 16C5 ...Repeated for Field RTD 6
" 16C6 ...Repeated for Field RTD 7
" 16C7 ...Repeated for Field RTD 8
Field Unit Transducer Actuals (Read Only) (8 Modules)
All except B90,
L60
16C8 Field Transducer 1 Value -32.768 to 32.767 --- 0.001 F004 0
" 16CA ...Repeated for Field Transducer 2
" 16CC ...Repeated for Field Transducer 3
" 16CE ...Repeated for Field Transducer 4
" 16D0 ...Repeated for Field Transducer 5
" 16D2 ...Repeated for Field Transducer 6
" 16D4 ...Repeated for Field Transducer 7
" 16D6 ...Repeated for Field Transducer 8
Frequency Rate of Change Actual Values (Read Only) (2 or 4 Modules)
D30, D60, F60,
G30, G60, L30,
L90, N60, T60
16E0 Frequency Rate of Change 1 -327.67 to 327.67 Hz/s 0.01 F002 0
" 16E1 Reserved (3 items) 0 to 65535 --- 1 F001 0
" 16E4 ...Repeated for Frequency Rate of Change 2
D60, F60, G30,
G60, L90, N60,
T60
16E8 ...Repeated for Frequency Rate of Change 3
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals