CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-33
2
Source Energy Metering (Read Only Non-Volatile) (4 or 6 Modules)
B30, C60, D60,
F35, F60, G30,
G60, L90, M60,
N60, T60
1D00 Source 1 Positive Watthour 0 to
1000000000000
Wh 0.001 F060 0
" 1D02 Source 1 Negative Watthour 0 to
1000000000000
Wh 0.001 F060 0
" 1D04 Source 1 Positive Varhour 0 to
1000000000000
varh 0.001 F060 0
" 1D06 Source 1 Negative Varhour 0 to
1000000000000
varh 0.001 F060 0
" 1D08 Reserved (8 items) --- --- --- F001 0
" 1D10 ...Repeated for Source 2
" 1D20 ...Repeated for Source 3
" 1D30 ...Repeated for Source 4
B30, F35, N60,
T60
1D40 ...Repeated for Source 5
" 1D50 ...Repeated for Source 6
Energy Commands (Read/Write Command)
B30, C60, D60,
F35, F60, G30,
G60, L90, M60,
N60, T60
1D60 Energy Clear Command 0 to 1 --- 1 F126 0 (No)
Source Frequency (Read Only) (2, 4, or 6 Modules)
All except B90,
C30
1D80 Frequency for Source 1 2 to 90 Hz 0.001 F003 0
" 1D82 Frequency for Source 2 2 to 90 Hz 0.001 F003 0
B30, C60, C70,
D60, F35, F60,
G30, G60, L60,
L90, M60, N60,
T35, T60
1D84 Frequency for Source 3 2 to 90 Hz 0.001 F003 0
" 1D86 Frequency for Source 4 2 to 90 Hz 0.001 F003 0
B30, C70, F35,
N60, T35, T60
1D88 Frequency for Source 5 2 to 90 Hz 0.001 F003 0
" 1D8A Frequency for Source 6 2 to 90 Hz 0.001 F003 0
Source Demand (Read Only) (4 or 6 Modules)
B30, C60, D60,
F35, F60, G60,
L60, L90, N60,
T60
1E00 Source 1 Demand Ia 0 to 999999.999 A 0.001 F060 0
" 1E02 Source 1 Demand Ib 0 to 999999.999 A 0.001 F060 0
" 1E04 Source 1 Demand Ic 0 to 999999.999 A 0.001 F060 0
" 1E06 Source 1 Demand Watt 0 to 999999.999 W 0.001 F060 0
" 1E08 Source 1 Demand Var 0 to 999999.999 var 0.001 F060 0
" 1E0A Source 1 Demand Va 0 to 999999.999 VA 0.001 F060 0
" 1E0C Reserved (4 items) --- --- --- F001 0
" 1E10 ...Repeated for Source 2
" 1E20 ...Repeated for Source 3
" 1E30 ...Repeated for Source 4
B30, F35, N60,
T60
1E40 ...Repeated for Source 5
" 1E50 ...Repeated for Source 6
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals