" 3731 Time of Day Timer 2 State 0 to 1 --- 1 F108 0 (Off)
" 3732 Time of Day Timer 3 State 0 to 1 --- 1 F108 0 (Off)
" 3733 Time of Day Timer 4 State 0 to 1 --- 1 F108 0 (Off)
" 3734 Time of Day Timer 5 State 0 to 1 --- 1 F108 0 (Off)
RADIUS Configuration (Read/Write Setting)
All 3735 Primary RADIUS IP Address 0 to 4294967295 --- 1 F003 0
" 3737 Primary Authentication Port 1 to 65535 --- 1 F001 1812
" 3738 Primary Accounting Port 1 to 65535 --- 1 F001 1813
" 3739 Secondary RADIUS IP Address 0 to 4294967295 --- 1 F003 0
" 373B Secondary Authentication Port 0 to 65535 --- 1 F001 1812
" 373D Secondary Accounting Port 0 to 65535 --- 1 F001 1813
" 373F RADIUS Authentication Method 0 to 2 --- 1 F619 0 (EAP-TTLS)
" 3740 RADIUS Vendor ID 1 to 65535 --- 1 F001 2910
" 3741 Authentication Timeout 0 to 9999 sec 1 F001 10
" 3742 Authentication Retries 0 to 9999 --- 1 F001 3
" 3743 RADIUS Authentication Shared Secret --- --- --- F202 (none)
PTP Basic Configuration (Read/Write Setting)
All 3750 PTP Strict Power Profile 0 to 1 --- 1 F102 0 (Disabled)
" 3751 PTP Domain Number 0 to 255 --- 1 F001 0
" 3752 PTP VLAN Priority 0 to 7 --- 1 F001 4
" 3753 PTP VLAN ID 0 to 4095 --- 1 F001 0
" 3754 PTP Basic Configuration Reserved (2 items) 0 to 1 --- 1 F001 0
PTP Port Configuration (Read/Write Setting) (3 Modules)
All 3756 PTP Port 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 3757 PTP Port 1 Path Delay Adder 0 to 60000 ns 1 F001 0
" 3758 PTP Port 1 Path Delay Asymmetry -1000 to 1000 ns 1 F002 0
" 3759 ...Repeated for PTP Port 2
" 375C ...Repeated for PTP Port 3
Real Time Clock Synchronizing Actuals (Read Only)
All 375F RTC Sync Source 0 to 5 --- 1 F624 0 (None)
" 3760 PTP GrandMaster ID 0 to 100 -- 1 F073 0
" 3764 Real Time Clock Accuracy 0 to 999999999 ns 1 F003 0
" 3766 PTP Port 1 State (3 items) 0 to 4 -- 1 F625 0 (Disabled)
" 3769 RTC Offset 0 to 999999999 ns 1 F004 0
" 376B PTP - IRIG-B Delta -500000000 to
500000000
ns 1 F004 0
Real Time Clock Synchronizing FlexAnalogs (Read Only)
All 376D PTP-IRIG-B Delta FlexAnalog -262143 to 262143 --- 1 F004 0
Capacitor Control Actual Values (Read Only) (3 Modules)
C70 3780 Capacitor Control 1 Discharge Time 0 to 3600 s 1 F001 0
" 3781 Capacitor Control 2 Discharge Time 0 to 3600 s 1 F001 0
" 3782 Capacitor Control 3 Discharge Time 0 to 3600 s 1 F001 0
Frequency Out-of-Band Accumulation Actual Values (Read Only)
G30, G60 37A0 Frequency OOB Accumulator Band 1
Accumulation (OvUnFrecAccActualBand_1)
0.0 to 999.9 % 0.1 F001 0
" 37A1 Frequency OOB Accumulator Band 2
Accumulation (OvUnFrecAccActualBand_2)
0.0 to 999.9 % 0.1 F001 0
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)

Related product manuals