2-58 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
Passwords (Read Only)
All 4028 Command Password Status 0 to 1 --- 1 F102 0 (Disabled)
" 4029 Setting Password Status 0 to 1 --- 1 F102 0 (Disabled)
Passwords (Read/Write Setting)
All 402A Command Password Access Timeout 5 to 480 min 1 F001 5
" 402B Setting Password Access Timeout 5 to 480 min 1 F001 30
" 402C Invalid Password Attempts (before lockout) 2 to 5 --- 1 F001 3
" 402D Password Lockout Duration 5 to 60 min 1 F001 5
Passwords (Read/Write)
All 402E Password Access Events 0 to 1 --- 1 F102 0 (Disabled)
Passwords (Read/Write Setting)
All 402F Local Setting Auth 1 to 4294967295 --- 1 F300 1
" 4031 Remote Setting Auth 0 to 4294967295 --- 1 F300 1
" 4033 Access Auth Timeout 5 to 480 min 1 F001 30
User Display Invoke (Read/Write Setting)
All 4040 Invoke and Scroll Through User Display
Menu Operand
0 to 4294967295 --- 1 F300 0
LED Test (Read/Write Setting)
All 4048 LED Test Function 0 to 1 --- 1 F102 0 (Disabled)
" 4049 LED Test Control 0 to 4294967295 --- 1 F300 0
Preferences (Read/Write Setting)
All 404F Language 0 to 7 --- 1 F531 0 (English)
" 4050 Flash Message Time 0.5 to 10 s 0.1 F001 10
" 4051 Default Message Timeout 10 to 900 s 1 F001 300
" 4052 Default Message Intensity 0 to 3 --- 1 F101 0 (25%)
" 4053 Screen Saver Feature 0 to 1 --- 1 F102 0 (Disabled)
" 4054 Screen Saver Wait Time 1 to 65535 min 1 F001 30
" 4055 Current Cutoff Level 0.002 to 0.02 pu 0.001 F001 20
" 4056 Voltage Cutoff Level 0.1 to 1 V 0.1 F001 10
87L Channel Status (Read Only)
L30 4059 Channel 1 Local Loopback Status 0 to 2 --- 1 F134 2 (n/a)
" 405A Channel 1 Loop Delay 0 to 200 ms 0.1 F001 0
" 405B Channel 1 Number of Lost Packets 0 to 65535 --- 1 F001 0
" 405C Channel 1 Remote Loopback Status 0 to 2 --- 1 F134 2 (n/a)
" 405D Channel 1 Status 0 to 2 --- 1 F134 1 (OK)
" 405E Channel 2 Local Loopback Status 0 to 2 --- 1 F134 2 (n/a)
" 405F Channel 2 Loop Delay 0 to 200 ms 0.1 F001 0
" 4060 Channel 2 Number of Lost Packets 0 to 65535 --- 1 F001 0
" 4061 Channel 2 Remote Loopback Status 0 to 2 --- 1 F134 2 (n/a)
" 4062 Channel 2 Status 0 to 2 --- 1 F134 2 (n/a)
" 4063 Channel PFLL Status 0 to 2 --- 1 F134 1 (OK)
" 4064 87L Network Status 0 to 2 --- 1 F134 2 (n/a)
87L Channel Status (Read/Write Command)
L30 4065 Channel Status Clear 0 to 1 --- 1 F126 0 (No)
87L Power System (Read/Write Setting)
L30 4068 Block GPS Time Reference 0 to 4294967295 --- 1 F300 0
" 406A Channel Asymmetry Compensation 0 to 4294967295 --- 1 F300 0
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE b30 and is the answer not in the manual?

GE b30 Specifications

General IconGeneral
Modelb30
ManufacturerGE
Coil VoltageN/A (Solid State Relay)
Coil PowerN/A (Solid State Relay)
Mechanical LifeN/A (Solid State Relay)
Electrical LifeN/A (Solid State Relay)