Page 11
Electromagnetic Compatibility Directive 89/336/EEC
Emissions standard EN 50081-2 1994 Industrial environment
Immunity standard EN 50082-2 1995 Industrial environment
(IEC 60801 parts 2, 3 and 4)
Susceptibility to Electrostatic
Discharge 8kV air discharge/4kV contact.
Warning: This specification applies when the front cover is fitted. If the front cover
is removed to gain access to the adjustment potentiometers then appropriate ESD
protection must be taken.
Low Voltage Directive 72/23/EEC
Designed to EN61010-1 1993 safety requirements.
Timers
Alarm time delay settings 1, 2, 4, 8, 16, 32, 64, 128s
(other settings available on
request)
Accuracy of setting ±10% (±0.25s)
Output relays
URGENT alarm relay 2 changeover contacts
NON-URGENT alarm relay 2 changeover contacts
Contact ratings
Max. switching power 60W; 62.5VA
Max. switching voltage 220V dc; 250V ac
Max. switching current 2A