GE Multilin D60 Line Distance Protection System B-39
APPENDIX B B.4 MEMORY MAPPING
B
5A0D Reserved (6 items) 0 to 1 --- 1 F001 0
5A13 ...Repeated for Phase Instantaneous Overcurrent 2
5A26 ...Repeated for Phase Instantaneous Overcurrent 3
5A39 ...Repeated for Phase Instantaneous Overcurrent 4
5A4C ...Repeated for Phase Instantaneous Overcurrent 5
5A5F ...Repeated for Phase Instantaneous Overcurrent 6
5A72 ...Repeated for Phase Instantaneous Overcurrent 7
5A85 ...Repeated for Phase Instantaneous Overcurrent 8
5A98 ...Repeated for Phase Instantaneous Overcurrent 9
5AAB ...Repeated for Phase Instantaneous Overcurrent 10
5ABE ...Repeated for Phase Instantaneous Overcurrent 11
5AD1 ...Repeated for Phase Instantaneous Overcurrent 12
Neutral Time Overcurrent (Read/Write Grouped Setting)6 Modules)
5B00 Neutral Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5B01 Neutral Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5B02 Neutral Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5B03 Neutral Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5B04 Neutral Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5B05 Neutral Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5B06 Neutral Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5B07 Neutral Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5B09 Neutral Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5B0A Neutral Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5B0B Reserved (6 items) 0 to 1 --- 1 F001 0
5B11 ...Repeated for Neutral Time Overcurrent 2
5B22 ...Repeated for Neutral Time Overcurrent 3
5B33 ...Repeated for Neutral Time Overcurrent 4
5B44 ...Repeated for Neutral Time Overcurrent 5
5B55 ...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 Modules)
5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5C01 Neutral Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5C02 Neutral Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5C04 Neutral Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5C07 Neutral Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5C08 Neutral Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5C09 Reserved (8 items) 0 to 1 --- 1 F001 0
5C11 ...Repeated for Neutral Instantaneous Overcurrent 2
5C22 ...Repeated for Neutral Instantaneous Overcurrent 3
5C33 ...Repeated for Neutral Instantaneous Overcurrent 4
5C44 ...Repeated for Neutral Instantaneous Overcurrent 5
5C55 ...Repeated for Neutral Instantaneous Overcurrent 6
5C66 ...Repeated for Neutral Instantaneous Overcurrent 7
5C77 ...Repeated for Neutral Instantaneous Overcurrent 8
5C88 ...Repeated for Neutral Instantaneous Overcurrent 9
5C99 ...Repeated for Neutral Instantaneous Overcurrent 10
5CAA ...Repeated for Neutral Instantaneous Overcurrent 11
5CBB ...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (B30, T35 1 per CT bank for 6 modules; all others 2 per CT bank for 12 modules)
5D00 Ground Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT