B-40 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
5D03 Ground Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5D07 Ground Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5D09 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5D0A Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5D0B Reserved (6 items) 0 to 1 --- 1 F001 0
5D11 ...Repeated for Ground Time Overcurrent 2
5D22 ...Repeated for Ground Time Overcurrent 3
5D33 ...Repeated for Ground Time Overcurrent 4
5D44 ...Repeated for Ground Time Overcurrent 5
5D55 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 Modules)
5DA0 Ground Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5DA1 Ground Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5DA2 Ground Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5DA3 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5DA4 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5DA5 Ground Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5DA7 Ground Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5DA8 Ground Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5DA9 Reserved (8 items) 0 to 1 --- 1 F001 0
5DB1 ...Repeated for Ground Instantaneous Overcurrent 2
5DC2 ...Repeated for Ground Instantaneous Overcurrent 3
5DD3 ...Repeated for Ground Instantaneous Overcurrent 4
5DE4 ...Repeated for Ground Instantaneous Overcurrent 5
5DF5 ...Repeated for Ground Instantaneous Overcurrent 6
5E06 ...Repeated for Ground Instantaneous Overcurrent 7
5E17 ...Repeated for Ground Instantaneous Overcurrent 8
5E28 ...Repeated for Ground Instantaneous Overcurrent 9
5E39 ...Repeated for Ground Instantaneous Overcurrent 10
5E4A ...Repeated for Ground Instantaneous Overcurrent 11
5E5B ...Repeated for Ground Instantaneous Overcurrent 12
Setting Groups (Read/Write Setting)
5F70 Setting Group for Modbus Comms (0 means group 1) 0 to 5 --- 1 F001 0
5F71 Setting Groups Block 0 to 4294967295 --- 1 F300 0
5F73 FlexLogic to Activate Groups 2 through 6 (5 items) 0 to 4294967295 --- 1 F300 0
5F7D Setting Group Function 0 to 1 --- 1 F102 0 (Disabled)
5F7E Setting Group Events 0 to 1 --- 1 F102 0 (Disabled)
Setting Groups (Read Only)
5F7F Current Setting Group 0 to 5 --- 1 F001 0
Setting Group Names (Read/Write Setting)
5F8C Setting Group 1 Name --- --- --- F203 (none)
5F94 Setting Group 2 Name --- --- --- F203 (none)
5F9C Setting Group 3 Name --- --- --- F203 (none)
5FA4 Setting Group 4 Name --- --- --- F203 (none)
5FAC Setting Group 5 Name --- --- --- F203 (none)
5FB4 Setting Group 6 Name --- --- --- F203 (none)
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 Modules)
6300 Negative Sequence Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
6301 Negative Sequence Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
6302 Negative Sequence Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
6303 Negative Sequence Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT