6304 Negative Sequence Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
6305 Negative Sequence Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
6306 Negative Sequence Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
6308 Negative Sequence Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
6309 Negative Sequence Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
630A Reserved (7 items) 0 to 1 --- 1 F001 0
6311 ...Repeated for Negative Sequence Time Overcurrent 2
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 Modules)
63C0 Negative Sequence Instantaneous OC 1 Function 0 to 1 --- 1 F102 0 (Disabled)
63C1 Negative Sequence Instantaneous OC 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
63C2 Negative Sequence Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
63C3 Negative Sequence Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
63C4 Negative Sequence Instantaneous OC 1 Reset Delay 0 to 600 s 0.01 F001 0
63C5 Negative Sequence Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
63C7 Negative Sequence Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
63C8 Negative Sequence Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
63C9 Reserved (8 items) 0 to 1 --- 1 F001 0
63D1 ...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting) (3 Modules)
6440 Negative Sequence Overvoltage Function 0 to 1 --- 1 F102 0 (Disabled)
6441 Negative Sequence Overvoltage Source 0 to 5 --- 1 F167 0 (SRC 1)
6442 Negative Sequence Overvoltage Pickup 0 to 1.25 pu 0.001 F001 300
6443 Negative Sequence Overvoltage Pickup Delay 0 to 600 s 0.01 F001 50
6444 Negative Sequence Overvoltage Reset Delay 0 to 600 s 0.01 F001 50
6445 Negative Sequence Overvoltage Block 0 to 4294967295 --- 1 F300 0
6447 Negative Sequence Overvoltage Target 0 to 2 --- 1 F109 0 (Self-reset)
6448 Negative Sequence Overvoltage Events 0 to 1 --- 1 F102 0 (Disabled)
6449 ...Repeated for module number 2
6452 ...Repeated for module number 3
Overfrequency (Read/Write Setting) (4 Modules)
6470 Overfrequency 1 Function 0 to 1 --- 1 F102 0 (Disabled)
6471 Overfrequency 1 Block 0 to 4294967295 --- 1 F300 0
6473 Overfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
6474 Overfrequency 1 Pickup 20 to 65 Hz 0.01 F001 6050
6475 Overfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 500
6476 Overfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 500
6477 Overfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
6478 Overfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
6479 Reserved (4 items) 0 to 1 --- 1 F001 0
647D ...Repeated for Overfrequency 2
648A ...Repeated for Overfrequency 3
6497 ...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0 Power Swing Detect Function 0 to 1 --- 1 F102 0 (Disabled)
65C1 Power Swing Detect Source 0 to 5 --- 1 F167 0 (SRC 1)
65C2 Power Swing Detect Mode 0 to 1 --- 1 F513 0 (Two Step)
65C3 Power Swing Detect Supervision 0.05 to 30 pu 0.001 F001 600
65C4 Power Swing Detect Forward Reach 0.1 to 500 ohms 0.01 F001 5000
65C5 Power Swing Detect Forward RCA 40 to 90 degrees 1 F001 75
65C6 Power Swing Detect Reverse Reach 0.1 to 500 ohms 0.01 F001 5000
65C7 Power Swing Detect Reverse RCA 40 to 90 degrees 1 F001 75
65C8 Power Swing Detect Outer Limit Angle 40 to 140 degrees 1 F001 120
65C9 Power Swing Detect Middle Limit Angle 40 to 140 degrees 1 F001 90
65CA Power Swing Detect Inner Limit Angle 40 to 140 degrees 1 F001 60
Table B–10: MODBUS MEMORY MAP (Sheet 33 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT