B-42 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
65CB Power Swing Detect Delay 1 Pickup 0 to 65.535 s 0.001 F001 30
65CC Power Swing Detect Delay 1 Reset 0 to 65.535 s 0.001 F001 50
65CD Power Swing Detect Delay 2 Pickup 0 to 65.535 s 0.001 F001 17
65CE Power Swing Detect Delay 3 Pickup 0 to 65.535 s 0.001 F001 9
65CF Power Swing Detect Delay 4 Pickup 0 to 65.535 s 0.001 F001 17
65D0 Power Swing Detect Seal In Delay 0 to 65.535 s 0.001 F001 400
65D1 Power Swing Detect Trip Mode 0 to 1 --- 1 F514 0 (Delayed)
65D2 Power Swing Detect Block 0 to 4294967295 --- 1 F300 0
65D4 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
65D5 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
65D6 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho Shape)
65D7 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
65D8 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
65D9 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
65DA Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
65DB Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DC Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DD Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DE Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DF Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65E0 Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65E1 Power Swing I2 Supervision Enable 0 to 4294967295 --- 1 F300 0
65E3 Power Swing I2 Supervision 0.05 to 30 pu 0.001 F001 200
Sensitive Directional Power (Read/Write Grouped Setting) (2 Modules)
6680 Sensitive Directional Power 1 Function 0 to 1 --- 1 F102 0 (Disabled)
6681 Sensitive Directional Power 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
6682 Sensitive Directional Power 1 RCA 0 to 359 degrees 1 F001 0
6683 Sensitive Directional Power 1 Calibration 0 to 0.95 degrees 0.05 F001 0
6684 Sensitive Directional Power 1 STG1 SMIN -1.2 to 1.2 pu 0.001 F002 100
6685 Sensitive Directional Power 1 STG1 Delay 0 to 600 s 0.01 F001 50
6686 Sensitive Directional Power 1 STG2 SMIN -1.2 to 1.2 pu 0.001 F002 100
6687 Sensitive Directional Power 1 STG2 Delay 0 to 600 s 0.01 F001 2000
6688 Sensitive Directional Power 1 Block 0 to 4294967295 --- --- F300 0
668A Sensitive Directional Power 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
668B Sensitive Directional Power 1 Events 0 to 1 --- 1 F102 0 (Disabled)
668C Reserved (5 items) 0 to 65535 --- 1 F001 0
6691 ...Repeated for Sensitive Directional Power 2
Load Encroachment (Read/Write Grouped Setting)
66C0 Load Encroachment Function 0 to 1 --- 1 F102 0 (Disabled)
66C1 Load Encroachment Source 0 to 5 --- 1 F167 0 (SRC 1)
66C2 Load Encroachment Minimum Voltage 0 to 3 pu 0.001 F001 250
66C3 Load Encroachment Reach 0.02 to 250 ohms 0.01 F001 100
66C4 Load Encroachment Angle 5 to 50 degrees 1 F001 30
66C5 Load Encroachment Pickup Delay 0 to 65.535 s 0.001 F001 0
66C6 Load Encroachment Reset Delay 0 to 65.535 s 0.001 F001 0
66C7 Load Encroachment Block 0 to 4294967295 --- 1 F300 0
66C9 Load Encroachment Target 0 to 2 --- 1 F109 0 (Self-reset)
66CA Load Encroachment Events 0 to 1 --- 1 F102 0 (Disabled)
66CB Reserved (6 items) 0 to 65535 --- 1 F001 0
Trip Output (Read/Write Setting)
6760 Trip Mode 0 to 2 --- 1 F195 0 (Disabled)
6761 Trip 3-Pole Input1 0 to 4294967295 --- 1 F300 0
6763 Trip 3-Pole Input2 0 to 4294967295 --- 1 F300 0
6765 Trip 3-Pole Input3 0 to 4294967295 --- 1 F300 0
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT