GE Multilin D60 Line Distance Protection System B-43
APPENDIX B B.4 MEMORY MAPPING
B
6767 Trip 3-Pole Input4 0 to 4294967295 --- 1 F300 0
6769 Trip 3-Pole Input5 0 to 4294967295 --- 1 F300 0
676B Trip 3-Pole Input6 0 to 4294967295 --- 1 F300 0
676D Trip 1-Pole Input1 0 to 4294967295 --- 1 F300 0
676F Trip 1-Pole Input2 0 to 4294967295 --- 1 F300 0
6771 Trip 1-Pole Input3 0 to 4294967295 --- 1 F300 0
6773 Trip 1-Pole Input4 0 to 4294967295 --- 1 F300 0
6775 Trip 1-Pole Input5 0 to 4294967295 --- 1 F300 0
6777 Trip 1-Pole Input6 0 to 4294967295 --- 1 F300 0
6779 Trip Reclose Input1 0 to 4294967295 --- 1 F300 0
677B Trip Reclose Input2 0 to 4294967295 --- 1 F300 0
677D Trip Reclose Input3 0 to 4294967295 --- 1 F300 0
677F Trip Reclose Input4 0 to 4294967295 --- 1 F300 0
6781 Trip Reclose Input5 0 to 4294967295 --- 1 F300 0
6783 Trip Reclose Input6 0 to 4294967295 --- 1 F300 0
6785 Trip Force 3-Pole 0 to 4294967295 --- 1 F300 0
6787 Trip Pilot Priority 0 to 65.535 s 0.001 F001 0
6788 Breaker Phase A Open 0 to 4294967295 --- 1 F300 0
678A Breaker Phase B Open 0 to 429496729 --- 1 F300 0
678C Breaker Phase C Open 0 to 429496729 --- 1 F300 0
6783 Trip Events 0 to 1 --- 1 F102 0 (Disabled)
678F Reverse Fault Operand 0 to 429496729 --- 1 F300 0
6791 Trip Delay On Evolving Faults 0 to 429496729 s 0.001 F001 0
6792 Trip Seal-In Delay 0 to 429496729 s 0.001 F001 0
6793 Trip Reset 0 to 2 --- 1 F609 0 (Pole Curr OR
Custom)
6794 Start Timer Zone 2 Phase Input 1 0 to 429496729 --- 1 F300 0
6796 Start Timer Zone 2 Phase Input 2 0 to 429496729 --- 1 F300 0
6798 Start Timer Zone 2 Ground Input 1 0 to 429496729 --- 1 F300 0
679A Start Timer Zone 2 Ground Input 2 0 to 429496729 --- 1 F300 0
679C Phase Selector Reset Delay 0.5 to 3 s 0.001 F001 500
679D Reserved (4 items) 0 to 1 --- 1 F001 0
Open Pole Detect (Read/Write Setting)
67B0 Open Pole Function 0 to 1 --- 1 F102 0 (Disabled)
67B1 Open Pole Block 0 to 4294967295 --- 1 F300 0
67B3 Open Pole Voltage Supervision 0 to 1 --- 1 F102 0 (Disabled)
67B4 Open Pole Current Pickup 0 to 30 pu 0.001 F001 50
67B5 Open Pole Target 0 to 2 --- 1 F109 0 (Self-reset)
67B6 Open Pole Events 0 to 1 --- 1 F102 0 (Disabled)
67B7 Open Pole Line XC0 300 to 9999.9 ohms 0.1 F003 99999
67B9 Open Pole Line XC1 300 to 9999.9 ohms 0.1 F003 99999
67BB Open Pole Remote Current Pickup 0 to 30 pu 0.001 F001 50
67BC Open Pole Detection 0 to 1 --- 1 F608 0 (I AND V AND
CBaux)
67BD Open Pole Mode 0 to 1 --- 1 F607 0 (Accelerated)
67BE Reserved (5 items) 0 to 1 --- 1 F001 0
Pilot DUTT (1P) (Read/Write Setting)
67D0 DUTT Function 0 to 1 --- 1 F102 0 (Disabled)
67D1 DUTT Seal In Delay 0 to 65.535 s 0.001 F001 0
67D2 DUTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
67D3 DUTT RX1 0 to 4294967295 --- 1 F300 0
67D5 DUTT RX2 0 to 4294967295 --- 1 F300 0
67D7 DUTT RX3 0 to 4294967295 --- 1 F300 0
67D9 DUTT RX4 0 to 4294967295 --- 1 F300 0
67DB DUTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 35 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT