GE Multilin D60 Line Distance Protection System B-47
APPENDIX B B.4 MEMORY MAPPING
B
7078 Phase Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7079 Phase Distance Zone 1 Events 0 to --- 1 F102 0 (Disabled)
707A Phase Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
707B Phase Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
707C Phase Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
707D Phase Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
707E Phase Distance Zone 1 Quad Right Blinder 0.02 to 500 ohms 0.01 F001 1000
707F Phase Distance Zone 1 Quad Right Blinder RCA 60 to 90 degrees 1 F001 85
7080 Phase Distance Zone 1 Quad Left Blinder 0.02 to 500 ohms 0.01 F001 1000
7081 Phase Distance Zone 1 Quad Left Blinder RCA 60 to 90 degrees 1 F001 85
7082 Phase Distance Zone 1 Volt Limit 0 to 5 pu 0.001 F001 0
7083 Phase Distance Zone 1 Transformer Voltage Connection 0 to 12 --- 1 F153 0 (None)
7084 Phase Distance Zone 1 Transformer Current Connection 0 to 12 --- 1 F153 0 (None)
7085 Phase Distance Zone 1 Rev Reach 0.02 to 500 ohms 0.01 F001 200
7086 Phase Distance Zone 1 Rev Reach RCA 30 to 90 degrees 1 F001 85
7087 Reserved (10 items) --- --- --- F001 0
7091 ...Repeated for Phase Distance Zone 2
70B2 ...Repeated for Phase Distance Zone 3
70D3 ...Repeated for Phase Distance Zone 4
70F4 ...Repeated for Phase Distance Zone 5
Ground Distance (Read/Write Grouped Setting) (5 Modules)
7130 Ground Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7131 Ground Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200
7132 Ground Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
7133 Ground Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
7134 Ground Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
7135 Ground Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
7136 Ground Distance Zone 1 Block 0 to 4294967295 --- 1 F300 0
7138 Ground Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7139 Ground Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
713A Ground Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
713B Ground Distance Zone 1 Z0 Z1 Magnitude 0 to 10 --- 0.01 F001 270
713C Ground Distance Zone 1 Z0 Z1 Angle -90 to 90 degrees 1 F002 0
713D Ground Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
713E Ground Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
713F Ground Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
7140 Ground Distance Zone 1 Quad Right Blinder 0.02 to 500 ohms 0.01 F001 1000
7141 Ground Distance Zone 1 Quad Right Blinder RCA 60 to 90 degrees 1 F001 85
7142 Ground Distance Zone 1 Quad Left Blinder 0.02 to 500 ohms 0.01 F001 1000
7143 Ground Distance Zone 1 Quad Left Blinder RCA 60 to 90 degrees 1 F001 85
7144 Ground Distance Zone 1 Z0M Z1 Magnitude 0 to 7 --- 0.01 F001 0
7145 Ground Distance Zone 1 Z0M Z1 Angle -90 to 90 degrees 1 F002 0
7146 Ground Distance Zone 1 Voltage Level 0 to 5 pu 0.001 F001 0
7147 Ground Distance Zone 1 Non-Homogeneous Angle -40 to 40 degrees 0.1 F002 0
7148 Ground Distance Zone 1 POL Current 0 to 1 --- 1 F521 0 (Zero-seq)
7149 Ground Distance Zone 1 Reverse Reach 0.02 to 500 ohms 0.01 F001 200
717A Ground Distance Zone 1 Reverse Reach RCA 30 to 90 degrees 1 F001 85
714B Reserved (7 items) 0 to 65535 --- 1 F001 0
7152 ...Repeated for Ground Distance Zone 2
7174 ...Repeated for Ground Distance Zone 3
7196 ...Repeated for Ground Distance Zone 4
71B8 ...Repeated for Ground Distance Zone 5
Line Pickup (Read/Write Grouped Setting)
71E0 Line Pickup Function 0 to 1 --- 1 F102 0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 39 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT