B-48 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
71E1 Line Pickup Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
71E2 Line Pickup Phase IOC Pickup 0 to 30 pu 0.001 F001 1000
71E3 Line Pickup UV Pickup 0 to 3 pu 0.001 F001 700
71E4 Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 150
71E5 Line End Open Reset Delay 0 to 65.535 s 0.001 F001 90
71E6 Line Pickup OV Pickup Delay 0 to 65.535 s 0.001 F001 40
71E7 Autoreclose Coordination Pickup Delay 0 to 65.535 s 0.001 F001 45
71E8 Autoreclose Coordination Reset Delay 0 to 65.535 s 0.001 F001 5
71E9 Autoreclose Coordination Bypass 0 to 1 --- 1 F102 1 (Enabled)
71EA Line Pickup Block 0 to 4294967295 --- 1 F300 0
71EC Line Pickup Target 0 to 2 --- 1 F109 0 (Self-reset)
71ED Line Pickup Events 0 to 1 --- 1 F102 0 (Disabled)
71EE Terminal Open 0 to 4294967295 --- 1 F300 0
71F0 Autoreclose Accelerate 0 to 4294967295 --- 1 F300 0
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 Modules)
7200 Phase Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7201 Phase Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7202 Phase Directional Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
7204 Phase Directional Overcurrent 1 ECA 0 to 359 --- 1 F001 30
7205 Phase Directional Overcurrent 1 Pol V Threshold 0 to 3 pu 0.001 F001 700
7206 Phase Directional Overcurrent 1 Block Overcurrent 0 to 1 --- 1 F126 0 (No)
7207 Phase Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7208 Phase Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7209 Reserved (8 items) 0 to 1 --- 1 F001 0
7211 ...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 Modules)
7230 Neutral Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7231 Neutral Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7232 Neutral Directional Overcurrent 1 Polarizing 0 to 4 --- 1 F230 0 (Voltage)
7233 Neutral Directional Overcurrent 1 Forward ECA -90 to 90 ° Lag 1 F002 75
7234 Neutral Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
7235 Neutral Directional Overcurrent 1 Forward Pickup 0.006 to 30 pu 0.001 F001 50
7236 Neutral Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
7237 Neutral Directional Overcurrent 1 Reverse Pickup 0.002 to 30 pu 0.001 F001 50
7238 Neutral Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7239 Neutral Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
723B Neutral Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
723C Neutral Directional Overcurrent 1 Polarizing Voltage 0 to 1 --- 1 F231 0 (Calculated V0)
723D Neutral Directional Overcurrent 1 Op Current 0 to 1 --- 1 F196 0 (Calculated 3I0)
723E Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
723F Neutral Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
7240 Reserved 0 to 1 --- 1 F001 0
7241 ...Repeated for Neutral Directional Overcurrent 2
Negative-sequence Directional Overcurrent (Read/Write Grouped Settings) (2 Modules)
7260 Negative Sequence Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7261 Negative Sequence Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7262 Negative Sequence Directional Overcurrent 1 Type 0 to 1 --- 1 F179 0 (Neg Sequence)
7263 Neg Sequence Directional Overcurrent 1 Forward ECA 0 to 90 ° Lag 1 F002 75
7264 Neg Seq Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
7265 Neg Sequence Directional Overcurrent 1 Forward Pickup 0.015 to 30 pu 0.05 F001 5
7266 Neg Seq Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
7267 Neg Sequence Directional Overcurrent 1 Reverse Pickup 0.015 to 30 pu 0.05 F001 5
7268 Negative Sequence Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 40 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT