GE Multilin D60 Line Distance Protection System B-61
APPENDIX B B.4 MEMORY MAPPING
B
A76C ...Repeated for Non-Volatile Latch 10
A778 ...Repeated for Non-Volatile Latch 11
A784 ...Repeated for Non-Volatile Latch 12
A790 ...Repeated for Non-Volatile Latch 13
A79C ...Repeated for Non-Volatile Latch 14
A7A8 ...Repeated for Non-Volatile Latch 15
A7B4 ...Repeated for Non-Volatile Latch 16
Pilot POTT (1P) (Read/Write Setting)
A800 POTT 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
A801 POTT 1P Permissive Echo 0 to 2 --- 1 F199 0 (Disabled)
A802 POTT 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
A803 POTT 1P Trans Block Pickup Delay 0 to 65.535 s 0.001 F001 20
A804 POTT 1P Trans Block Reset Delay 0 to 65.535 s 0.001 F001 90
A805 POTT 1P Echo Duration 0 to 65.535 s 0.001 F001 100
A806 POTT 1P Echo Lockout 0 to 65.535 s 0.001 F001 250
A807 POTT 1P Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 50
A808 POTT 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
A809 POTT 1P Ground Directional Overcurrent Forward 0 to 4294967295 --- 1 F300 0
A80B POTT 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
A80C POTT 1P Rx1 0 to 4294967295 --- 1 F300 0
A80E POTT 1P Rx2 0 to 4294967295 --- 1 F300 0
A810 POTT 1P Rx3 0 to 4294967295 --- 1 F300 0
A812 POTT 1P Rx4 0 to 4294967295 --- 1 F300 0
A814 POTT 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
A815 POTT 1P Event 0 to 1 --- 1 F102 0 (Disabled)
A816 POTT 1P Echo Condition 0 to 4294967295 --- 1 F300 0
A818 POTT 1P Scheme Block 0 to 4294967295 --- 1 F300 0
A81A Reserved (22 items) 0 to 1 --- 1 F001 0
Pilot POTT1 (1P) (Read/Write Setting)
A830 POTT1 1P Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
A831 POTT1 1P Permissive Echo 0 to 2 --- 1 F199 0 (Disabled)
A832 POTT1 1P Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
A833 POTT1 1P Trans Block Pickup Delay 0 to 65.535 s 0.001 F001 20
A834 POTT1 1P Trans Block Reset Delay 0 to 65.535 s 0.001 F001 90
A835 POTT1 1P Echo Duration 0 to 65.535 s 0.001 F001 100
A836 POTT1 1P Echo Lockout 0 to 65.535 s 0.001 F001 250
A837 POTT1 1P Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 50
A838 POTT1 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
A839 POTT1 1P Ground Directional Overcurrent Forward 0 to 4294967295 --- 1 F300 0
A83B POTT1 1P Number of Communication Bits 0 to 2 --- 1 F198 0 (1)
A83C POTT1 1P Rx1 0 to 4294967295 --- 1 F300 0
A83E POTT1 1P Rx2 0 to 4294967295 --- 1 F300 0
A840 POTT1 1P Rx3 0 to 4294967295 --- 1 F300 0
A842 POTT1 1P Rx4 0 to 4294967295 --- 1 F300 0
A844 POTT1 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
A845 POTT1 1P Event 0 to 1 --- 1 F102 0 (Disabled)
A846 POTT1 1P Echo Condition 0 to 4294967295 --- 1 F300 0
A848 POTT1 1P Scheme Block 0 to 4294967295 --- 1 F300 0
A84A POTT1 1P OC Fwd2 0 to 4294967295 --- 1 F300 0
A84C POTT1 1P OC Fwd2 0 to 4294967295 --- 1 F300 0
A84E Reserved (22 items) 0 to 1 --- 1 F001 0
Pilot Blocking 1 (1P) (Read/Write Setting)
A864 Blocking 1 Scheme 1P Function 0 to 1 --- 1 F102 0 (Disabled)
A865 Blocking 1 Scheme 1PBlock 0 to 4294967295 --- 1 F300 0
Table B–10: MODBUS MEMORY MAP (Sheet 53 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT