B-62 D60 Line Distance Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
A867 Block 1 1P Rx Coord Pickup Delay 0 to 65.535 s 0.001 F001 10
A868 Block 1 1P Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 30
A869 Block 1 1P Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
A86A Blocking 1 Scheme 1P Seal in Delay 0 to 65.535 s 0.001 F001 0
A86B Blocking 1 Scheme 1P Dir Fwd 1 0 to 4294967295 --- 1 F300 0
A86D Blocking 1 Scheme 1P Dir Fwd 2 0 to 4294967295 --- 1 F300 0
A86F Blocking 1 Scheme 1P Dir Fwd 3 0 to 4294967295 --- 1 F300 0
A871 Blocking 1 Scheme 1P Dir Rev 1 0 to 4294967295 --- 1 F300 0
A873 Blocking 1 Scheme 1P Dir Rev 2 0 to 4294967295 --- 1 F300 0
A875 Blocking 1 Scheme 1P Dir Rev 3 0 to 4294967295 --- 1 F300 0
A877 Blocking 1 Scheme 1P Force Tx Stop 1 0 to 4294967295 --- 1 F300 0
A879 Blocking 1 Scheme 1P Force Tx Stop 2 0 to 4294967295 --- 1 F300 0
A87B Blocking 1 Scheme 1P Comm Bits 0 to 2 --- 1 F198 0 (1)
A87C Blocking 1 Scheme 1P Rx1 0 to 4294967295 --- 1 F300 0
A87E Blocking 1 Scheme 1P Rx2 0 to 4294967295 --- 1 F300 0
A880 Blocking 1 Scheme 1P Rx3 0 to 4294967295 --- 1 F300 0
A882 Blocking 1 Scheme 1P Rx4 0 to 4294967295 --- 1 F300 0
A884 Blocking 1 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
A885 Blocking 1 1P Event 0 to 1 --- 1 F102 0 (Disabled)
Frequency Rate of Change (Read/Write Setting) (4 Modules)
A900 Frequency Rate of Change 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A901 Frequency Rate of Change 1 OC Supervision 0 to 30 pu 0.001 F001 200
A902 Frequency Rate of Change 1 Min 20 to 80 Hz 0.01 F001 4500
A903 Frequency Rate of Change 1 Max 20 to 80 Hz 0.01 F001 6500
A904 Frequency Rate of Change 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
A905 Frequency Rate of Change 1 Reset Delay 0 to 65.535 s 0.001 F001 0
A906 Frequency Rate of Change 1 Block 0 to 4294967295 --- 1 F300 0
A908 Frequency Rate of Change 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A909 Frequency Rate of Change 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A90A Frequency Rate of Change 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A90B Frequency Rate of Change 1 Trend 0 to 2 --- 1 F224 0 (Increasing)
A90C Frequency Rate of Change 1 Pickup 0.1 to 15 Hz/s 0.01 F001 50
A90D Frequency Rate of Change 1 OV Supervision 0.1 to 3 pu 0.001 F001 700
A90E Frequency Rate of Change 1 Reserved (3 items) 0 to 1 --- 1 F001 0
A911 ...Repeated for Frequency Rate of Change 2
A922 ...Repeated for Frequency Rate of Change 3
A933 ...Repeated for Frequency Rate of Change 4
IEC 61850 Received Analog Settings (Read/Write) (32 Modules)
AA00 IEC 61850 GOOSE analog 1 default value –1000000 to 1000000 --- 0.001 F060 1000
AA02 IEC 61850 GOOSE analog input 1 mode 0 to 1 --- 1 F491 0 (Default Value)
AA03 IEC 61850 GOOSE analog input 1 units --- --- --- F207 (none)
AA05 IEC 61850 GOOSE analog input 1 per-unit base 0 to 999999999.999 --- 0.001 F060 1
AA07 ...Repeated for IEC 61850 GOOSE analog input 2
AA0E ...Repeated for IEC 61850 GOOSE analog input 3
AA15 ...Repeated for IEC 61850 GOOSE analog input 4
AA1C ...Repeated for IEC 61850 GOOSE analog input 5
AA23 ...Repeated for IEC 61850 GOOSE analog input 6
AA2A ...Repeated for IEC 61850 GOOSE analog input 7
AA31 ...Repeated for IEC 61850 GOOSE analog input 8
AA38 ...Repeated for IEC 61850 GOOSE analog input 9
AA3F ...Repeated for IEC 61850 GOOSE analog input 10
AA46 ...Repeated for IEC 61850 GOOSE analog input 11
AA4D ...Repeated for IEC 61850 GOOSE analog input 12
AA54 ...Repeated for IEC 61850 GOOSE analog input 13
Table B–10: MODBUS MEMORY MAP (Sheet 54 of 77)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT