GE Multilin G60 Generator Protection System 4-29
4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE
4
By default, when an incorrect Command or Setting password has been entered via any external communications interface
three times within three minutes, the REMOTE ACCESS DENIED FlexLogic™ operand is set to On and the G60 does not
allow settings or command access via the any external communications interface for five minutes. The REMOTE ACCESS
DENIED
FlexLogic™ operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings pass-
word.
These default settings can be changed in EnerVista under Settings > Product Setup > Security.