EasyManua.ls Logo

GE G60

GE G60
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Multilin G60 Generator Protection System 2-25
2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS
2
2.2.8 FIELD AND STATOR GROUND MODULES
GPM-F MODULE CONTACT INPUTS
Internal wetting: 24 V DC
Input comparator threshold: 6 V DC
External contact: dry
Current when energized: < 10 mA
Debounce time: 10 ms
GPM-F MODULE CRITICAL FAILURE RELAY
Make and carry: 30 A for 0.2 s as per ANSI C37.90
Continuous carry: 8 A
Break (DC inductive, L/R = 40 ms): 1 A at 24 V, 0.5 A at 48 V,
0.3 A at 125 V, 0.2 A at 250 V
Operate time: < 8 ms
Contact material: silver alloy
GPM-F MODULE POWER SUPPLY
GPM-F-L: 100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
GPM-F-HM: 100 to 240V AC at 50/60Hz and 10 VA
125 to 250V DC at 10W
GPM-S-G MODULE CONTACT INPUTS
Internal wetting: 24 V DC
Input comparator threshold: 6 V DC
External contact: dry
Current when energized: < 10 mA
Debounce time: 10 ms
GPM-S-G MODULE POWER SUPPLY
Power supply: 100 to 240 V AC at 50/60 Hz and 110VA
125 to 250 V DC at 110W
Output ratings: 26 V rectangular at 20 Hz, load capabil-
ity 80 VA
GPM-S-B MODULE
Power rating: 80VA
Input ratings: maximum 30 V rectangular at 20 Hz
GPM-F-R MODULE
Current limiting resistor: 12.5 × 4
Voltage divider resistor: 5 × 3
STATOR GROUND PROTECTION CT
Part number: 204-SD-43737
Turns ratio: 400:5A
Rating factor (RF): 3.0
Frequency: 20 Hz
Voltage insulation: 600 V
Basic impulse level (BIL): 10 kV

Table of Contents

Related product manuals