GE Multilin G60 Generator Protection System 5-189
5 SETTINGS 5.6 GROUPED ELEMENTS
5
Figure 5–88: PHASE DIRECTIONAL SCHEME LOGIC
5.6.7 NEUTRAL CURRENT
a) MAIN MENU
PATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6)  NEUTRAL CURRENT
NEUTRAL CURRENT
NEUTRAL TOC1
See page 5–190.
MESSAGE
NEUTRAL IOC1
See page 5–191.
MESSAGE
NEUTRAL
DIRECTIONAL OC1
See page 5–192.
MESSAGE
NEUTRAL
DIRECTIONAL OC2
See page 5–192.
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
SETTING
SETTING
SETTING
SETTING
SETTING
SETTING
PHASE DIR 1
FUNCTION:
PHASE DIR 1 SOURCE:
PHASE DIR 1 BLOCK OC
WHEN V MEM EXP:
PHASE DIR 1
BLOCK:
PHASE DIR 1 ECA:
PHASE DIR 1 POL V
THRESHOLD:
PH DIR1 BLK A
PH DIR1 BLK B
PH DIR1 BLK C
PH DIR1 BLK
IA
No
Seq=ABC Seq=ACB
Yes
VBC VCB
827078A7.CDR
Off=0
V MINIMUM
-Use V when V Min
-Use V memory when
V < Min
I 0.05 pu
Enabled=1
AND
AND
OR
MEMORY TIMER
1 cycle
1 sec
Vpol
0
I
1
RUN
AND
PHASE B LOGIC SIMILAR TO PHASE A
PHASE C LOGIC SIMILAR TO PHASE A
OR
USE ACTUAL VOLTAGE
USE MEMORIZED VOLTAGE