Loading...
GE Multilin G60 Generator Protection System 5-17
5 SETTINGS 5.2 PRODUCT SETUP
5
For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following.
Figure 5–3: SUPERVISORY PANEL
For the Security panel, the following settings are available.
RADIUS Server Settings
SETTING NAME DESCRIPTION MIN MAX DEFAULT UNITS MINIMUM
PERMISSION
Primary RADIUS IP
Address
IP address of the main RADIUS server.
Default value indicates no Primary
RADIUS server is configured, and hence
RADIUS is disabled.
0.0.0.0 223.255.255.254 0.0.0.0 - Administrator
Primary
Authentication Port
RADIUS authentication port 1 65535 1812 - Administrator
Primary Accounting
Port
RADIUS accounting port 1 65535 1813 - Administrator
Vendor ID An identifier that specifies RADIUS
vendor-specific attributes used with the
protocol
Value that
represents
General
Electric
Administrator
RADIUS
Authentication
(Shared) Secret
Shared secret used in authentication. It
displays as asterisks. This setting must
meet the CyberSentry password
requirements.
See the
following
password
section for
requirements
See the following
password section
for requirements
N/A - Administrator
RADIUS
Authentication
Method
Authentication method used by RADIUS
server. Currently fixed to EAP-TTLS.
EAP-TTLS EAP-TTLS EAP-TTLS - Administrator
Timeout Timeout in seconds between re-
transmission requests
0 9999 10 sec Administrator
Retries Number of retries before giving up 0 9999 3 - Administrator