5-118 G60 Generator Protection System GE Multilin
5.4 SYSTEM SETUP 5 SETTINGS
5
MODIFICATION OF SYNC WORD IN CFG-2 FOR TR 90-5 DATA SETS
In the CFG-2 file, all relevant information about the data being streamed is included. However, this file does not include the
fact that it describes a 90-5 dataset or the number of Application Service Data Units (datasets). In order to communicate
this information via the CFG-2 file for a given aggregator, when the aggregator is set to 90-5, the version number of the
CFG-2 file (found in bits 0-3 of the frame SYNC word - which should presently be set to 2) is set as follows:
The PMU settings are organized in logical groups as follows.
PATH: SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PHASOR MEASUREMENT UNIT 1
VALUE
(DECIMAL)
# OF ASDUS
11 1
12 2
13 3
14 4
PHASOR MEASUREMENT
UNIT 1
PMU 1 BASIC
CONFIGURATION
See page 5-119.
MESSAGE
PMU 1
CALIBRATION
See page 5-123.
MESSAGE
PMU 1
TRIGGERING
See page 5-124.
MESSAGE
PMU 1
RECORDING
See page 5-132.