5-156 G60 Generator Protection System GE Multilin
5.5 FLEXLOGIC 5 SETTINGS
5
Figure 5–62: FLEXELEMENT DIRECTION, PICKUP, AND HYSTERESIS
In conjunction with the
FLEXELEMENT 1 INPUT MODE setting the element could be programmed to provide two extra charac-
teristics as shown in the figure below.
Figure 5–63: FLEXELEMENT INPUT MODE SETTING
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over
PICKUP
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under
PICKUP
HYSTERESIS = % of PICKUP
842705A1.CDR
842706A2.CDR
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;