EasyManua.ls Logo

GE G60

GE G60
780 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-248 G60 Generator Protection System GE Multilin
5.6 GROUPED ELEMENTS 5 SETTINGS
5
The difference in angle can be used as the SH CT ANGLE COMPEN setting. The preferred method of doing this is by
inserting a resistance equal to the SH STATOR GND STG2 PICKUP setting at the neutral of the generator and compensat-
ing the angle at this setting.
SH STATOR GND OC PICKUP: This setting specifies the backup overcurrent pickup level based on sub-harmonic cur-
rent. This protection can be used in addition to the sub-harmonic injection based 100% ground fault and fundamental
phasor over voltage based 95% ground fault protection. One per-unit value of current is the sensitive ground CT sec-
ondary rating setting, which is always 5 A since the CT used is rated for 5 A secondary.
SH STATOR GND OC DELAY: This setting specifies a time delay for sub-harmonic current based backup over current
protection. Thermal capabilities of the loading resistor or neutral grounding transformer should be considered while
setting this delay.
SH STATOR GND Vsupv: The 20 Hz source can be monitored using this voltage supervision. This setting in pu pro-
vides the voltage level below which if the sub-harmonic voltage phasor magnitude remains for a period of 10 seconds,
the
SH STAT GND TRB OP operand will be asserted. One per-unit value of voltage is the auxiliary VT nominal secondary
voltage setting or the equivalent primary voltage if used in primary. A typical setting of 1 V is suggested. However,
when the neutral grounding transformer’s load resistance is less than 0.5 ohms, the use of voltage supervision is not
recommended.
SH STATOR GND Isupv: The 20 Hz source can be monitored using this current supervision. This setting in per-unit
values provides the current level below which if the sub-harmonic current phasor magnitude remains for a period of 10
seconds, the
SH STAT GND TRB OP operand will be asserted. One per-unit current is the sensitive ground CT second-
ary rating setting or the primary rating if used in primary. A typical setting of 0.002 pu (=10 mA in secondary) is recom-
mended with the provided 5 A secondary CT.
The logic for the sub-harmonic stator ground fault feature is shown below.
Figure 5–132: SUB-HARMONIC STATOR GROUND FAULT LOGIC
6(77,1*6
(QDEOHG
)XQFWLRQ
2II
%ORFN
$&78$/9$/8(
7UDFNLQJ)UHTXHQF\
&203$5$725
+]I+]
6(77,1*6
5V!
)XQFWLRQ
5S!
)XQFWLRQ
$&78$/9$/8(6
9DX[6+
,JQG6+
&$/&8/$7(
&DOFXODWH
UHVLVWDQFH
$1'
6(77,1*
6WDJH3LFNXS
581
5J3LFNXS
6(77,1*
6WDJH3LFNXS
581
5J3LFNXS
6(77,1*
*URXQG2&3LFNXS
581
,JQG3LFNXS
6(77,1*
&XUUHQW6XSHUYLVLRQ
581
,JQG3LFNXS
6(77,1*
9ROWDJH6XSHUYLVLRQ
581
9[3LFNXS
25
6(77,1*
6WDJH3LFNXS'HOD\
7
3.3
6(77,1*
6WDJH3LFNXS'HOD\
7
3.3
6(77,1*
*URXQG2&'HOD\
7
3.3
7,0(5
VHF
)/(;/2*,&23(5$1'6
6+67$725*1'67*23
6+67$725*1'67*3.3
6+67$725*1'67*'32
)/(;/2*,&23(5$1'6
6+67$725*1'67*23
6+67$725*1'67*3.3
6+67$725*1'67*'32
)/(;/2*,&23(5$1'6
6+67$725*1'2&23
6+67$725*1'2&3.3
6+67$725*1'2&'32
)/(;/2*,&23(5$1'6
6+67$725*1'75%23
6+67$725*1' 3.375%
6+67$725*1''3275%
$&78$/9$/8(6
6WDWRU*URXQG5HVLVWDQFH
6+,QMHFWLRQ$PSV
6+,QMHFWLRQ9ROWV
$&'5

Table of Contents

Related product manuals