EasyManua.ls Logo

GE GL 313 F3/4031 P/VR - Mounting the Guide Shaft

GE GL 313 F3/4031 P/VR
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RECONDITIONING
82 OI 248 (EN) REV6 /REV6
10.1.9 Mounting the Guide Shaft
Insert the interrupter unit (5) and the movable contact system (6)
into the fixed contact (7) so that the shaft holes in the guide levers
(8) and fixed contact (7) are lined up.
Place the spacer sleeve (21) between the levers.
Connect the guide lever and fixed contact to the guide shaft (28).
Coat a new screw (22) with locking adhesive per S1.
Fasten the shaft with the locking plate (23) and the new screw
(22). Tighten to a torque of 17Nm.
5 Interrupter unit 1x
6 Movable contact system 1x
7 Fixed contact 1x
8Guide lever 2x
17 Socket head cap screw, M8x12 A2-70 1x
21 Spacer sleeve 1x
23 Locking plate 1x
28 Guide shaft 1x
5
6
7
8
23
22
21
28
BA-P-PS-9